CU Compressed 5/8kV NLEPR Insulation 133/100% IL ARMOR-X® PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial - VFD Cable
- Southwire #
- SPEC46255
Type MV-105 Three Conductor Copper, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Continuous Corrugated Welded Aluminum Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket. Suitable for VFD Applications. Type MC HL. Silicone Free
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (15) ↓Available sizes & constructions
| Cond. Size | Cond. Strands | Diameter Over Conductor (in)(cm) | Diameter Over Insulation (in)(cm) | Insulation Thickness (mils)(mm) | Diameter Over Shield (in)(cm) | Ground Size | Diameter Over Armor (in)(cm) | Jacket Thickness (mils)(mm) | Approx. OD (inches)(cm) | Approx. Weight (lbs/1000')(kgs/km) | Max Pull Tension (lbs)(kg) | Min. Bend Radius (in)(cm) | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2 AWG2 AWG | 77 | 0.2820.72 | 0.5451.38 | 1152.92 | 0.6051.54 | 3x103x10 | 1.6704.24 | 701.78 | 1.8104.60 | 19032832 | 1592722.12 | 12.632.00 | 89063689 |
| 1 AWG1 AWG | 1919 | 0.3220.82 | 0.5901.50 | 1152.92 | 0.6501.65 | 3x83x8 | 1.8454.69 | 701.78 | 1.9855.04 | 22083286 | 2008910.81 | 13.835.05 | 89063799 |
| 1/0 AWG1/0 AWG | 1919 | 0.3610.92 | 0.6301.60 | 1152.92 | 0.6901.75 | 3x83x8 | 2.0405.18 | 601.52 | 2.1605.49 | 25243756 | 25341149.40 | 15.138.35 | 89063889 |
| 2/0 AWG2/0 AWG | 1919 | 0.4051.03 | 0.6741.71 | 1152.92 | 0.7341.86 | 3x83x8 | 2.0405.18 | 601.52 | 2.1605.49 | 27994165 | 31941448.77 | 15.138.35 | 89063989 |
| 4/0 AWG4/0 AWG | 1919 | 0.5121.30 | 0.7661.95 | 1152.92 | 0.8262.10 | 3x63x6 | 2.2905.82 | 751.91 | 2.4406.20 | 39865932 | 50782303.34 | 17.043.18 | 89064089 |
| 250 KCMIL250 KCMIL | 3737 | 0.5581.42 | 0.8182.08 | 1152.92 | 0.8782.23 | 3x63x6 | 2.2905.82 | 751.91 | 2.4406.20 | 46926982 | 60002721.55 | 17.043.18 | 89064199 |
| 350 KCMIL350 KCMIL | 3737 | 0.6611.68 | 0.9172.33 | 1152.92 | 0.9772.48 | 3x63x6 | 2.5506.48 | 751.91 | 2.7006.86 | 59018782 | 84003810.17 | 18.948.01 | 89064289 |
| 500 KCMIL500 KCMIL | 3737 | 0.7892.00 | 1.0422.65 | 1152.92 | 1.1022.80 | 3x43x4 | 2.8807.32 | 751.91 | 3.0307.70 | 753311210 | 120005443.10 | 21.253.85 | 89064389 |
| 750 KCMIL750 KCMIL | 6161 | 0.9682.46 | 1.2543.19 | 1152.92 | 1.3143.34 | 3x43x4 | 3.5408.99 | 852.16 | 3.7109.42 | 1096916324 | 180008164.66 | 25.965.79 | 89064499 |
| 2 AWG2 AWG | 0.1620.24 | 0.2040.30 | 0.0340.05 | 0.0400.06 | 0.336 + j0.2170.336 + j0.217 | 0.024 + j0.0390.024 + j0.039 | 19201920 | 135135 | 145145 | 140140 | 154154 | 89063689 | |
| 1 AWG1 AWG | 0.1280.19 | 0.1620.24 | 0.0310.05 | 0.0390.06 | 0.336 + j0.2200.336 + j0.220 | 0.020 + j0.0350.020 + j0.035 | 20442044 | 155155 | 165165 | 160160 | 180180 | 89063799 | |
| 1/0 AWG1/0 AWG | 0.1020.15 | 0.1280.19 | 0.0280.04 | 0.0370.06 | 0.336 + j0.2200.336 + j0.220 | 0.020 + j0.0350.020 + j0.035 | 21652165 | 175175 | 190190 | 185185 | 205205 | 89063889 | |
| 2/0 AWG2/0 AWG | 0.0810.12 | 0.1020.15 | 0.0260.04 | 0.0360.05 | 0.336 + j0.2200.336 + j0.220 | 0.020 + j0.0350.020 + j0.035 | 23022302 | 200200 | 220220 | 215215 | 240240 | 89063989 | |
| 4/0 AWG4/0 AWG | 0.0510.08 | 0.0650.10 | 0.0210.03 | 0.0340.05 | 0.336 + j0.2200.336 + j0.220 | 0.020 + j0.0350.020 + j0.035 | 26332633 | 265265 | 280280 | 285285 | 320320 | 89064089 | |
| 250 KCMIL250 KCMIL | 0.0430.06 | 0.0560.08 | 0.0200.03 | 0.0330.05 | 0.336 + j0.2210.336 + j0.221 | 0.020 + j0.0350.020 + j0.035 | 28002800 | 290290 | 315315 | 320320 | 355355 | 89064199 | |
| 350 KCMIL350 KCMIL | 0.0310.05 | 0.0410.06 | 0.0180.03 | 0.0320.05 | 0.337 + j0.2160.337 + j0.216 | 0.024 + j0.0360.024 + j0.036 | 31203120 | 355355 | 380380 | 395395 | 440440 | 89064289 | |
| 500 KCMIL500 KCMIL | 0.0220.03 | 0.0300.04 | 0.0150.02 | 0.0300.04 | 0.337 + j0.2160.337 + j0.216 | 0.024 + j0.0360.024 + j0.036 | 35163516 | 430430 | 460460 | 485485 | 545545 | 89064389 | |
| 750 KCMIL750 KCMIL | 0.0140.02 | 0.0230.03 | 0.0130.02 | 0.0290.04 | 0.341 + j0.2180.341 + j0.218 | 0.027 + j0.0360.027 + j0.036 | 41024102 | 530530 | 570570 | 615615 | 685685 | 89064499 |
Part numbers in this family (15)
| Southwire # | Description | Construction | Conductor Color | Packaging | |
|---|---|---|---|---|---|
| 2 AWG (2) | |||||
| 89063699 | 2-7 3/C CPRESS CU NL-EPR 25% T/S 3X#10 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 2 AWG 3C 7 STR | 1-BLACK/BLACK-/BLACK-/10 AWG BARE GRND/10 AWG BARE GRND/10 AWG BARE GRND | CUT TO LENGTH REEL | |
| 89063689 | 2-7 3/C CPRESS CU NL-EPR 25% T/S 3X#10 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET 2500 FT | 2 AWG 3C 7 STR | 1-BLACK/BLACK-/BLACK-/10 AWG BARE GRND/10 AWG BARE GRND/10 AWG BARE GRND | 2500 FT REEL | |
| 1 AWG (1) | |||||
| 89063799 | 1-19 3/C CPRESS CU NL-EPR 25% T/S 3X#8 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 1 AWG 3C 19 STR | 1-BLACK/BLACK-/BLACK-/8 AWG BARE GRND/8 AWG BARE GRND/8 AWGBARE GRND | CUT TO LENGTH REEL | |
| 1/0 AWG (2) | |||||
| 89063899 | 1/0-19 3/C CPRESS CU NL-EPR 25% T/S 3X#8 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 1/0 AWG 3C 19 STR | 1-BLACK/BLACK-/BLACK-/8 AWG BARE GRND/8 AWG BARE GRND/8 AWGBARE GRND | CUT TO LENGTH REEL | |
| 89063889 | 1/0-19 3/C CPRESS CU NL-EPR 25% T/S 3X#8 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET 2000 FT | 1/0 AWG 3C 19 STR | 1-BLACK/BLACK-/BLACK-/8 AWG BARE GRND/8 AWG BARE GRND/8 AWGBARE GRND | 2000 FT REEL | |
| 2/0 AWG (2) | |||||
| 89063999 | 2/0-19 3/C CPRESS CU NL-EPR 25% T/S 3X#8 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 2/0 AWG 3C 19 STR | 1-BLACK/BLACK-/BLACK-/8 AWG BARE GRND/8 AWG BARE GRND/8 AWGBARE GRND | CUT TO LENGTH REEL | |
| 89063989 | 2/0-19 3/C CPRESS CU NL-EPR 25% T/S 3X#8 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET 2000 FT | 2/0 AWG 3C 19 STR | 1-BLACK/BLACK-/BLACK-/8 AWG BARE GRND/8 AWG BARE GRND/8 AWGBARE GRND | 2000 FT REEL | |
| 4/0 AWG (2) | |||||
| 89064099 | 4/0-19 3/C CPRESS CU NL-EPR 25% T/S 3X#6 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 4/0 AWG 3C 19 STR | 1-BLACK/BLACK-/BLACK-/6 AWG BARE GRND/6 AWG BARE GRND/6 AWGBARE GRND | CUT TO LENGTH REEL | |
| 89064089 | 4/0-19 3/C CPRESS CU NL-EPR 25% T/S 3X#6 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET 2000 FT | 4/0 AWG 3C 19 STR | 1-BLACK/BLACK-/BLACK-/6 AWG BARE GRND/6 AWG BARE GRND/6 AWGBARE GRND | 2000 FT REEL | |
| 250 kcmil (1) | |||||
| 89064199 | 250-37 3/C CPRESS CU NL-EPR 25% T/S 3X#6 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 250 KCMIL 3C 37S | 1-BLACK/BLACK-/BLACK-/6 AWG BARE GRND/6 AWG BARE GRND/6 AWGBARE GRND | CUT TO LENGTH REEL | |
| 350 kcmil (2) | |||||
| 89064299 | 350-37 3/C CPRESS CU NL-EPR 25% T/S 3X#6 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 350 KCMIL 3C 37 STR | 1-BLACK/BLACK-/BLACK-/6 AWG BARE GRND/6 AWG BARE GRND/6 AWGBARE GRND | CUT TO LENGTH REEL | |
| 89064289 | 350-37 3/C CPRESS CU NL-EPR 25% T/S 3X#6 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET 1500 FT | 350 KCMIL 3C 37 STR | 1-BLACK/BLACK-/BLACK-/6 AWG BARE GRND/6 AWG BARE GRND/6 AWGBARE GRND | 1500 FT REEL | |
| 500 kcmil (2) | |||||
| 89064399 | 500-37 3/C CPRESS CU NL-EPR 25% T/S 3X#4 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 500 KCMIL 3C 37S | 1-BLACK/BLACK-/BLACK-/4 AWG BARE GRND/4 AWG BARE GRND/4 AWGBARE GRND | CUT TO LENGTH REEL | |
| 89064389 | 500-37 3/C CPRESS CU NL-EPR 25% T/S 3X#4 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET 1300 FT | 500 KCMIL 3C 37S | 1-BLACK/BLACK-/BLACK-/4 AWG BARE GRND/4 AWG BARE GRND/4 AWGBARE GRND | 1300 FT REEL | |
| 750 kcmil (1) | |||||
| 89064499 | 750-61 3/C CPRESS CU NL-EPR 25% T/S 3X#4 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET | 750 KCMIL 3C 61S | 1-BLACK/BLACK-/BLACK-/4 AWG BARE GRND/4 AWG BARE GRND/4 AWGBARE GRND | CUT TO LENGTH REEL | |
Application & features
Southwire’s 5KV ARMOR-X® MC HL are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application. Rated for 1000 lbs./FT maximum sidewall pressure.
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- UL 1072 Medium-Voltage Power Cables
- UL 1569 Metal-Clad Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661