2/0-19 3/C CPRESS CU NL-EPR 25% T/S 3X#8 CU GW ARMOR-X MC-HL OR MV-105 5KV 133%/8KV 100% V YELLOW PVC JACKET 2000 FT
- Southwire #
- 89063989
Type MV-105 Three Conductor Copper, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Continuous Corrugated Welded Aluminum Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket. Suitable for VFD Applications. Type MC HL. Silicone Free
Part of the family: CU Compressed 5/8kV NLEPR Insulation 133/100% IL ARMOR-X® PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial - VFD Cable
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 5KV ARMOR-X® MC HL are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications
| Cond. Size | 2/0 AWG2/0 AWG |
|---|---|
| Cond. Strands | 1919 |
| Diameter Over Conductor | 0.405 inch1.03 cm |
| Diameter Over Insulation | 0.674 inch1.71 cm |
| Insulation Thickness | 115 mils2.92 mm |
| Diameter Over Shield | 0.734 inch1.86 cm |
| Ground Size | 3x83x8 |
| Diameter Over Armor | 2.040 inch5.18 cm |
| Jacket Thickness | 60 mils1.52 mm |
| Approx. OD | 2.160 inch5.49 cm |
| Approx. Weight | 2799 lbs/1000'4165 kgs/km |
| Max Pull Tension | 3194 lbs1448.77 kg |
| Min. Bend Radius | 15.1 inch38.35 cm |
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- UL 1072 Medium-Voltage Power Cables
- UL 1569 Metal-Clad Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661