DistributorSouthwire

Southwire

CU Compressed 2.4kV EPR Insulation LSZH-TS Jacket. MV 90

Southwire #
SPEC46003

Type MV-90 Single Conductor Copper, Ethylene Propylene Rubber (EPR) Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket. Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (3) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Diameter Over Insulation (in)(cm)Insulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)Conduit Size (in)(cm)
2 AWG2 AWG770.2820.720.571.451253.18802.030.7411.88426634530240.405.914.992.56.35 95854699
2/0 AWG2/0 AWG19190.4051.030.6951.771253.18802.030.8712.2169010271064482.626.917.532.56.35 95357099
500 KCMIL500 KCMIL37370.7892.001.092.771403.561102.791.3323.382091311240001814.3710.626.92410.16 61117899
2 AWG2 AWG0.1620.240.2040.300.0430.060.186 + j0.0230.186 + j0.0230.193 + j0.0320.193 + j0.032145145155155190190215215 95854699
2/0 AWG2/0 AWG0.0810.120.1020.150.0390.060.084 + j0.0190.084 + j0.0190.092 + j0.0270.092 + j0.027220220235235300300330330 95357099
500 KCMIL500 KCMIL0.0220.030.0300.040.0340.050.012 + j0.0140.012 + j0.0140.02 + j0.0230.02 + j0.023470470505505695695775775 61117899

Part numbers in this family (3)

By size:
Southwire #DescriptionConstructionPackaging
958546992-7 CU 125 MILS EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)2 AWG 1C 7SCUT TO LENGTH REEL
953570992/0-19 CU 125 MILS EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)2/0 AWG 1C 19SCUT TO LENGTH REEL
61117899500-37 CU 140 MILS EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)500 KCMIL 1C 37SCUT TO LENGTH REEL

Application & features

Southwire’s 2.4kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold bend. Rated for 1000 lb/ft maximum sidewall pressure. Silicone Free.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • CT USE Sizes 1/0 AWG and Larger
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • AREMA 10.3.13 Recommended Design Criteria for Low-Smoke Halogen Free (LSHF) Polymeric Cable Jackets