DistributorSouthwire

Southwire

2-7 CU 125 MILS EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)

Southwire #
95854699

Type MV-90 Single Conductor Copper, Ethylene Propylene Rubber (EPR) Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket. Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire’s 2.4kV cables are suited for use in wet and dry areas, conduits, ducts, troughs, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold bend. Rated for 1000 lb/ft maximum sidewall pressure. Silicone Free.

Specifications

Cond. Size2 AWG2 AWG
Cond. Strands77
Diameter Over Conductor0.282 inch0.72 cm
Diameter Over Insulation0.57 inch1.45 cm
Insulation Thickness125 mils3.18 mm
Jacket Thickness80 mils2.03 mm
Approx. OD0.741 inch1.88 cm
Approx. Weight426 lbs/1000'634 kgs/km
Max Pull Tension530 lbs240.40 kg
Min. Bend Radius5.9 inch14.99 cm
Conduit Size2.5 inch6.35 cm

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • CT USE Sizes 1/0 AWG and Larger
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • AREMA 10.3.13 Recommended Design Criteria for Low-Smoke Halogen Free (LSHF) Polymeric Cable Jackets