DistributorSouthwire

Southwire

CU 600V PVC-Nylon Insulation PVC Jacket TFN Shielded. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Southwire #
SPEC45154

Type TC-ER, PLTC, FPL, and NFPL Control Cable 600 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation TFN Polyvinyl Chloride (PVC) Jacket, Shielded Control Cable Conductor Identification Method 1 Table 2

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (13) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsInsulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)DC Resistance at 25C (ohms/1000')(ohms/km)AC Resistance at 75C (ohms/1000')(ohms/km)Min. Bend Radius (in)(cm)Allowable Ampacity Raceway 75CAllowable Ampacity Raceway 90C
18 AWG18 AWG2277150.38451.140.1740.44131919286.6699.928.03511.962.15.331414 57645902
18 AWG18 AWG4477150.38451.140.3030.77233457856.6699.928.03511.963.69.14--1111 58609407
18 AWG18 AWG6677150.38451.140.3650.933349811216.6699.928.03511.964.411.18--1111 57788802
16 AWG16 AWG2277150.38451.140.2980.76213152774.1816.225.0377.503.69.14--1818 57788302
16 AWG16 AWG3377150.38451.140.2200.56294339584.1816.225.0377.502.66.60--1818 57788402
16 AWG16 AWG4477200.51451.140.3240.824060751124.1816.225.0377.503.99.91--1414 7716144408
16 AWG16 AWG161677200.51601.520.5741.461362022373534.1816.225.0377.506.917.53--99 6682510208
16 null16 null2277150.38451.140.2980.76213152774.1816.225.0377.503.69.14--1818 57788399

Part numbers in this family (13)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
18 AWG · 2 conductors (2)
5764599918-7 2/C CU TFN/PVC BLACK/RED TYPE TC 600V BLACK18 AWG 2C 7 STRBLACK/REDCUT TO LENGTH REEL
5764590218-7 2/C CU TFN/PVC BLACK/RED TYPE TC 600V BLACK 1000 FT18 AWG 2C 7 STRBLACK/RED1000 FT REEL
18 AWG · 4 conductors (2)
5860949918-7 4/C CU TFN/PVC BLACK/RED/BLUE/ORANGE TYPE TC-ER/PLTC BLACK18 AWG 4C 7 STRBLACK/RED/BLUE/ORANGECUT TO LENGTH REEL
5860940718-7 4/C CU TFN/PVC BLACK/RED/BLUE/ORANGE TYPE TC-ER/PLTC BLACK 2500 FT18 AWG 4C 7 STRBLACK/RED/BLUE/ORANGE2500 FT REEL
18 AWG · 6 conductors (1)
5778880218-7 6/C CU TFN/PVC BLACK/RED/WHITE/GREEN/BROWN/BLUE TYPE TC-ER 600V BLACK 1000 FT18 AWG 6C 7 STRBLACK/RED/WHITE/GREEN/BROWN/BLUE1000 FT REEL
16 AWG · 2 conductors (1)
5778830216-7 2/C CU FPL/TC/PLTC/PVC BLACK/RED TYPE TC/PLTC BLACK 1000 FT16 AWG 2C 7 STRBLACK/RED1000 FT REEL
16 AWG · 3 conductors (2)
5778849916/1 TRIAD STR CU TFN/PVC OAS TYPE TC-ER BLACK16 AWG 3C 7SBLACK/WHITE/REDCUT TO LENGTH REEL
5778840216/1 TRIAD STR CU TFN/PVC OAS TYPE TC-ER BLACK 1000 FT16 AWG 3C 7SBLACK/WHITE/RED1000 FT REEL
16 AWG · 4 conductors (1)
771614440816-7 4/C CU TFN/PVC BLACK/RED/BLUE/ORANGE TYPE TC-ER 600V BLACK 0 FT16 AWG 4C 7 STRBLACK/RED/BLUE/ORANGECUT TO LENGTH REEL
16 AWG · 16 conductors (3)
668251440816-7 16/C CU TFN/PVC TYPE TC-ER/PLTC BLACK 0 FT16 AWG 16C 7SBLACK/RED/BLUE/ORANGE/YELLOW/BROWN/RED-BLACK STRIPE/BLUE-BLACK STRIPE/ORANGE-BLACK STRIPE/YELLOW-BLACK STRIPE/BROWN-BLACK STRIPE/BLACK-RED STRIPE/BLUE-RED STRIPE/ORANGE-RED STRIPE/YELLOW-RED STRIPE/BROWN-RED STRIPECUT TO LENGTH REEL
668251020816-7 16/C CU TFN/PVC TYPE TC-ER/PLTC BLACK 1000 FT16 AWG 16C 7SBLACK/RED/BLUE/ORANGE/YELLOW/BROWN/RED-BLACK STRIPE/BLUE-BLACK STRIPE/ORANGE-BLACK STRIPE/YELLOW-BLACK STRIPE/BROWN-BLACK STRIPE/BLACK-RED STRIPE/BLUE-RED STRIPE/ORANGE-RED STRIPE/YELLOW-RED STRIPE/BROWN-RED STRIPE1000 FT REEL
668251850816-7 16/C CU TFN/PVC TYPE TC-ER/PLTC BLACK 8800 FT16 AWG 16C 7SBLACK/RED/BLUE/ORANGE/YELLOW/BROWN/RED-BLACK STRIPE/BLUE-BLACK STRIPE/ORANGE-BLACK STRIPE/YELLOW-BLACK STRIPE/BROWN-BLACK STRIPE/BLACK-RED STRIPE/BLUE-RED STRIPE/ORANGE-RED STRIPE/YELLOW-RED STRIPE/BROWN-RED STRIPE8800 FT REEL
Other (1)
5778839916/2C STR BC OAS RED/BLK PVC/NYL PVC TYPnull nullnull null

Application & features

Southwire’s Type TC-ER, PLTC, FPL, and NFPL Control Cable are suited for use in dry and wet areas, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in dry locations, 105°C for emergency overload, and 250°C For uses in Class I, II, and III per NEC Article 725 and 760. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Oil and sunlight resistant

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 13 Power-Limited Circuit Cables
  • UL 66 Fixture Wire
  • UL 1277 TC-ER
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • EPA 40 CFR, Part 26, Subpart C heavy metals per Table 1, TCLP method