16-7 4/C CU TFN/PVC BLACK/RED/BLUE/ORANGE TYPE TC-ER 600V BLACK 0 FT

Southwire #
7716144408

Type TC-ER, PLTC, FPL, and NFPL Control Cable 600 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation TFN Polyvinyl Chloride (PVC) Jacket, Shielded Control Cable Conductor Identification Method 1 Table 2

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire’s Type TC-ER, PLTC, FPL, and NFPL Control Cable are suited for use in dry and wet areas, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in dry locations, 105°C for emergency overload, and 250°C For uses in Class I, II, and III per NEC Article 725 and 760. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Oil and sunlight resistant

Specifications

Cond. Size16 AWG16 AWG
Conductor Number44
Cond. Strands77
Insulation Thickness20 mils0.51 mm
Jacket Thickness45 mils1.14 mm
Approx. OD0.324 inch0.82 cm
Copper Weight40 lbs/1000'60 kgs/km
Approx. Weight75 lbs/1000'112 kgs/km
DC Resistance at 25C4.181 ohms/1000'6.22 ohms/km
AC Resistance at 75C5.037 ohms/1000'7.50 ohms/km
Min. Bend Radius3.9 inch9.91 cm
Allowable Ampacity Raceway 75C--
Allowable Ampacity Raceway 90C1414

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 13 Power-Limited Circuit Cables
  • UL 66 Fixture Wire
  • UL 1277 TC-ER
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • EPA 40 CFR, Part 26, Subpart C heavy metals per Table 1, TCLP method