DistributorSouthwire

Southwire

CU 600/1000V XLPE Insulation ARMOR-X® Thermoplastic LSZH-TP Jacket XHHW-2. VFD Cable - CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Southwire #
SPEC45302

Type MC-HL Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Continuous Corrugated Welded Armor - ARMOR-X®, Thermoplastic Solonon® Low Smoke Zero Halogen (LSZH-TP) Jacket with Bare Copper Grounds

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (3) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Armor (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)
4 AWG4 AWG770.2250.57451.140.9202.34501.271.0202.5971810691001454.057.118.03 64769999
2/0 AWG2/0 AWG19190.4051.03551.401.4703.73501.271.5764.001992296431941448.7711.027.94 67267399
3/0 AWG3/0 AWG19190.4561.16551.401.5403.91601.521.6604.222427361240271826.6111.629.46 58667499
4 AWG4 AWG0.2580.380.3100.460.0220.030.0480.07 64769999
2/0 AWG2/0 AWG0.0810.120.0970.140.0160.020.0430.06 67267399
3/0 AWG3/0 AWG0.0640.100.0780.120.0140.020.0420.06 58667499

Part numbers in this family (3)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
647699994-7 3/C CPRESS CU XHHW-2 1X#8 CU GW ARMOR-X JACKET HL MC-HL 600V BLACK SOLONON JACKET4 AWG 3C 7 STR1-BLACK/2-RED/3-BLUE/8 AWG BARE GRNDCUT TO LENGTH REEL
672673992/0-19 3/C CPRESS CU XHHW-2 3X#10 CU GW ARMOR-X MC-HL 600V BLACK SOLONON JACKET2/0 AWG 3C 19 STR1-BLACK/2-RED/3-BLUE/10 AWG BARE GRND/10 AWG BARE GRND/10 AWG BARE GRNDCUT TO LENGTH REEL
586674993/0-19 3/C CPRESS CU XHHW-2 3X#8 CU GW ARMOR-X MC-HL 600V BLACK SOLONONJACKET3/0 AWG 3C 19 STR1-BLACK/2-RED/3-BLUE/8 AWG BARE GRND/8 AWG BARE GRND/8 AWG BARE GRNDCUT TO LENGTH REEL

Application & features

Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Cables with 3 ground wires suitable for VFD application.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA S-138-738 Power Cables Rated 2000 Volts or Less for use Between Variable Frequency Drives and Motors
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test