DistributorSouthwire

Southwire

3/0-19 3/C CPRESS CU XHHW-2 3X#8 CU GW ARMOR-X MC-HL 600V BLACK SOLONONJACKET

Southwire #
58667499

Type MC-HL Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Continuous Corrugated Welded Armor - ARMOR-X®, Thermoplastic Solonon® Low Smoke Zero Halogen (LSZH-TP) Jacket with Bare Copper Grounds

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Cables with 3 ground wires suitable for VFD application.

Specifications

Cond. Size3/0 AWG3/0 AWG
Cond. Strands1919
Diameter Over Conductor0.456 inch1.16 cm
Insulation Thickness55 mils1.40 mm
Diameter Over Armor1.540 inch3.91 cm
Jacket Thickness60 mils1.52 mm
Approx. OD1.660 inch4.22 cm
Approx. Weight2427 lbs/1000'3612 kgs/km
Max Pull Tension4027 lbs1826.61 kg
Min. Bend Radius11.6 inch29.46 cm

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA S-138-738 Power Cables Rated 2000 Volts or Less for use Between Variable Frequency Drives and Motors
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test