Cable de potencia 69 kV XLPE Laminate

Núm. Southwire
HVUD15

Forro de laminado de cobre o aluminio XLPE de pared estándar de SW, disponible hasta 6.000 kcmil.

Precio bajo cotización — el cobre cambia a diario (COMEX), por eso cotizamos con el precio vigente.

Cotizar por WhatsApp

Tamaños y construcciones disponibles

Tamaño (kcmil¹)(mm^2)Diámetro del Conductor (inches)(mm)Espesor del Aislamiento (inch)(cm)Diámetro Sobre Aislamiento (inch)(cm)Diámetro de Cubierta General (inch)(cm)Radio de Curvatura Mín. (inch)(inch)CapacitanciaCorriente de Carga (A/kft)Peso del Cable² (lbs/ft)Peso del Cable² (lbs/ft)
50012.700.741.88354899.161.543.912.105.3338/2638/2665.8765.870.990.993.643.642.632.63
75019.050.912.31354899.161.714.342.285.7942/2842/2876.0176.011.141.144.574.573.033.03
100025.401.062.69354899.161.884.782.466.2545/3045/3085.6085.601.291.295.505.503.433.43
125031.751.193.02354899.162.005.082.606.6047/3247/3293.1393.131.401.406.336.333.773.77
150038.101.323.35354899.162.135.412.746.9650/3350/33100.69100.691.511.517.227.224.124.12
175044.451.433.63354899.162.265.742.887.3252/3552/35108.23108.231.631.638.138.134.514.51
200050.801.503.81354899.162.355.972.977.5454/3654/36113.10113.101.701.708.988.984.824.82
250063.501.814.605001270.003.007.623.709.4067/4467/44100.20100.201.511.5111.8011.806.206.20
300076.201.975.005001270.003.168.033.889.8670/4770/47106.73106.731.601.6013.4013.406.906.90
350088.902.075.265001270.003.268.283.9810.1172/4872/48110.93110.931.671.6715.4015.407.507.50
4000101.602.245.695001270.003.438.714.1610.5775/5075/50117.88117.881.771.7717.7017.708.308.30
5000127.002.496.325001270.003.689.354.4211.2380/5380/53128.02128.021.921.9221.7021.709.809.80
6000152.402.676.785001270.003.869.804.6211.7383/5683/56135.54135.542.042.0425.1025.1010.3010.30
50012.706206207474520520626249049059594104104949
75019.057707709292640640767661061073735105106161
100025.40900900108108740740888871071085855905907171
125031.7510101010121121830830999980080096966606607979
150038.10110011001311319009001081088808801051057207208686
175044.45118011801411419609601151159609601151157807809393
200050.801250125014914910101010121121102010201221228308309999
250063.50147014701761761240124014814811601160139139920920110110
300076.2016101610192192135013501611611290129015415410801080129129
350088.9017301730207207145014501731731400140016716711701170140140
4000101.6018401840220220152015201821821500150017917912501250149149
5000127.0020302030243243168016802012011720172020620614301430171171
6000152.40527527

Aplicación y características

Se utiliza predominantemente para transmisión subterránea en sistemas de tubo conduit, adecuado para uso en lugares húmedos o secos, enterramiento directo, ductos subterráneos y donde esté expuesto a la luz solar. Debe utilizarse a 69,000 voltios o menos y a temperaturas del conductor que no excedan 90°C para operación normal.

Normas y referencias

  • Max Voltage Rating: 72.5 kV
  • BIL Rating: 350 kV
  • Nominal Conductor: 90 °C
  • Max. Emergency Conductor: 105 °C
  • Short Circuit Conductor: 250 °C
  • Minimum Installation: -10 °C
  • Design Standards: AEIC, ICEA, IEC
  • Factory Test Voltages: 80 kV / 60 min.
  • XLPE Loss Factor: 0.0005
  • Relative Permittivity: 2.3