TCU 600V NLEPR Insulation Thermoset LSZH-TS Jacket RHH/RHW-2/USE-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Southwire #
SPEC45010

Power Cable 600Volt Single Conductor Tinned Copper, No Lead Ethylene Propylene Rubber (NL-EPR) insulation RHH/RHW-2/USE-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket. CT Rated 1/0 and Larger - Sunlight Resistant - For Direct Burial - Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (2) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)
500 KCMIL500 KCMIL1137370.7892.00751.91651.651.0892.771543229617982676 67424401
500 KCMIL500 KCMIL115.413.7240001814.370.0220.030.0290.040.0390.06380380430430 67424401

Part numbers in this family (2)

Southwire #DescriptionConstructionPackaging
500 kcmil (2)
67424499500-37 TINNED CU 75 NL-EPR/65 LSZH 600V RHH/RHW-2/USE-2 BLACK500 KCMIL 1C 37SCUT TO LENGTH REEL
67424401500-37 TINNED CU 75 NL-EPR/65 LSZH 600V RHH/RHW-2/USE-2 BLACK 1000 FT500 KCMIL 1C 37S1000 FT REEL

Application & features

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Rated for 1000 lbs./FT maximum sidewall pressure.

a. NEC compliant
b. Passes UL VW-1
c. 70,000 BTU/Hr. Vertical Flame Test
d. UL listed for CT use on 1/0 and Larger
e. IEEE 1202 and ST-1 (1/0 and larger)
f. -40°C Cold impact and cold bend
g. Oil Resistant I and II
h. UV/Sunlight resistant black color
i. Color Available upon request

Standards & references

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 FT4-ST1 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)