TCU 600V NLEPR Insulation Thermoset LSZH-TS Jacket RHH/RHW-2/USE-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
- Southwire #
- SPEC45010
Power Cable 600Volt Single Conductor Tinned Copper, No Lead Ethylene Propylene Rubber (NL-EPR) insulation RHH/RHW-2/USE-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket. CT Rated 1/0 and Larger - Sunlight Resistant - For Direct Burial - Silicone Free
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (2) ↓Available sizes & constructions
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in)(cm) | Insulation Thickness (mils)(mm) | Jacket Thickness (mils)(mm) | Approx. OD (inches)(cm) | Copper Weight (lbs/1000')(kgs/km) | Approx. Weight (lbs/1000')(kgs/km) | |
|---|---|---|---|---|---|---|---|---|---|
| 500 KCMIL500 KCMIL | 11 | 3737 | 0.7892.00 | 751.91 | 651.65 | 1.0892.77 | 15432296 | 17982676 | 67424401 |
| 500 KCMIL500 KCMIL | 11 | 5.413.72 | 40001814.37 | 0.0220.03 | 0.0290.04 | 0.0390.06 | 380380 | 430430 | 67424401 |
Part numbers in this family (2)
Application & features
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Rated for 1000 lbs./FT maximum sidewall pressure.
a. NEC compliant
b. Passes UL VW-1
c. 70,000 BTU/Hr. Vertical Flame Test
d. UL listed for CT use on 1/0 and Larger
e. IEEE 1202 and ST-1 (1/0 and larger)
f. -40°C Cold impact and cold bend
g. Oil Resistant I and II
h. UV/Sunlight resistant black color
i. Color Available upon request
Standards & references
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1685 FT4-ST1 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- CT USE Sizes 1/0 AWG and Larger
- NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)