DistributorSouthwire

Southwire

Southwire® Machine Flex® CU 600/1000V THHN Insulation Black TPE Jacket. Silicone-Free

Southwire #
SPEC45047

Type TC-ER Machine Tray Power Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4. Silicone-Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (11) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)AC Resistance at 75C (ohms/1000')(ohms/km)Min. Bend Radius (in)(cm)Allowable Ampacity Raceway 75CAllowable Ampacity Raceway 90C
8 AWG8 AWG331681680.1530.39300.76651.650.6271.591572343164700.8611.282.56.3550505555 65367299
8 AWG8 AWG441681680.1530.39300.76651.650.7001.782103133755580.8611.282.87.1140404444 67732399
8 AWG8 AWG551681680.1530.39300.76651.650.7661.952633914516710.8611.283.07.6240404444 65300799
6 AWG6 AWG442592590.1980.50300.76651.650.8172.083585335648390.5410.813.28.1352526060 67732499
4 AWG4 AWG444204200.2350.60401.02802.030.9692.4653279283212380.3400.513.89.6568687676 67732599
2 AWG2 AWG336516510.3020.77401.021002.541.0642.7063794898714690.2160.325.313.46115115130130 65296899
2 AWG2 AWG446516510.3020.77401.021002.541.1963.048491263126718860.2160.325.914.999292104104 67732699
1/0 AWG1/0 AWG33106410640.3540.90601.52802.031.3183.3512301830169425210.1260.196.616.76150150170170 67429899
2/0 AWG2/0 AWG33133013300.4001.02601.52802.031.4183.6014852210202130080.1010.157.118.03175175195195 67430099
350 KCMIL350 KCMIL338938930.8092.05701.781102.792.0195.1334975204446166390.0410.0612.130.73310310350350 67757399
600 KCMIL600 KCMIL33148014801.1252.86802.031403.562.7096.88584186927207107250.0260.0416.341.40420420475475 67757699

Part numbers in this family (11)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
653672998-168 3/C CU PVC/NYLON CDRS/TPE PHASE ID TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 2587 600V BLACK8 AWG 3C 168 STR1-ONE/2-TWOCUT TO LENGTH REEL
677323998-168 4/C CU PVC/NYLON CDRS/TPE PHASE ID TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 2587 600V BLACK8 AWG 4C 168SBLACK/BLACK/BLACK/GREEN-YELLOWOWCUT TO LENGTH REEL
653007998-168 5/C CU PVC/NYLON CDRS/TPE PHASE ID TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 2587 600V BLACK8 AWG 5C 168S1-ONE/2-TWO/3-THREE/4-FOUR/GREEN-YELLOW STRIPE/-CUT TO LENGTH REEL
677324996-259 4/C CU PVC/NYLON CDRS/TPE PHASE ID TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 2587 600V BLACK6 AWG 4C 259SBLACK/BLACK/BLACK/GREEN-YELLOWOWCUT TO LENGTH REEL
677325994-420 4/C CU PVC/NYLON CDRS/TPE PHASE ID TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 2587 600V BLACK4 AWG 4C 420S1-ONE/2-TWO/3-THREE/GREEN-YELLOW STRIPECUT TO LENGTH REEL
652968992-651 3/C CU PVC/NYLON CDRS/TPE PHASE ID TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 2587 600V BLACK2 AWG 3C 651S1-ONE/2-TWO/GREEN-YELLOW STRIPE/-CUT TO LENGTH REEL
677326992-651 4/C CU PVC/NYLON CDRS/TPE PHASE ID TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 2587 600V BLACK2 AWG 4C 651S1-ONE/2-TWO/3-THREE/GREEN-YELLOW STRIPECUT TO LENGTH REEL
674298991/0-1064 3/C CU THHN/TPE PHASE ID 1X#2 GG TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 20886 CSA AWM I/II A/B 600V BLACK1/0 AWG 3C 1064S1-ONE/2-TWO/3-THREE/GREEN-YELLOW STRIPECUT TO LENGTH REEL
674300992/0-1330 3/C CU THHN/TPE PHASE ID 1X#2 GG TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 20886 CSA AWM I/II A/B 600V BLACK2/0 AWG 3C 1330S1-ONE/2-TWO/3-THREECUT TO LENGTH REEL
67757399350-893 3/C CU THHN/TPE PHASE ID 1X#2 GG TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 20886 CSA AWM I/II A/B 600V BLACK350 KCMIL 3C 893S1-ONE/2-TWO/3-THREE/GREEN-YELLOW STRIPECUT TO LENGTH REEL
67757699600-1480 3/C CU THHN/TPE PHASE ID 1X#2 GG TYPE TC-ER/WTTC/MTW FLEXING/DP-1 AWM 20886 CSA AWM I/II A/B 600V BLACK600 KCMIL 3C 1480S1-ONE/2-TWO/3-THREE/GREEN-YELLOW STRIPECUT TO LENGTH REEL

Application & features

Southwire’s Machine Flex® tray power cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Southwire’s machine tray cable is ideal to power CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Power-Limited Circuit Cables
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 AWM Style 2587
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2250 Instrumentation Tray Cable
  • UL 2277 Type WTTC
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Exceeds Ecolab PM-40-1 Material Resistance Test With 30-day Exposure, UL Verified V747862
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661