
![]()
VFD JACKETED MC (ACWU90) RHW-2/CPE 2,000 Volt Copper
VFD2KGC4/3 VFD JACKETED MC (ACWU90) RHW-2/CPE 2,000 Volt Copper 4 AWG 3C
- Service Wire #
- VFD2KGC4/3
Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RHW-2) , phase identified and cabled together with suitable fillers and three symmetrical bare copper ground conductors. Cable core shielded with 5-mil copper tape, helically applied with 50% overlap for 100% coverage and double tape thickness throughout the cable. Shielded core covered with galvanized steel interlocked armor with overall black CPE jacket. Available with aluminum armor or PVC or EnviroPlus ® (LSZH) jacket. Available with 50% grounds*.
Part of the family: VFD JACKETED MC (ACWU90) RHW-2/CPE 2,000 Volt Copper
Application & features
Application
For use in VFD applications. Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2, Class III - Div 1 and 2 *Patented for use with ServiceDrive ® connector and termination kit.
Specifications
| Voltage Rating | 2 kV (2,000 V)2 kV |
|---|---|
| Certifications | Made in the USA, REACH, ROHS, Rockwell, ULMade in the USA, REACH, ROHS, Rockwell, UL |
| Construction | 4 AWG 3C4 AWG 3C |
| Strand | 77 |
| Insulation Thickness | 8080 |
| Grounding Conductors | (3) #12(3) #12 |
| Diameter Over Armor | 1.071.07 |
| Jacket Thickness | 5050 |
| Approx. Diameter Overall | 1.171.17 |
| Approx. Net Weight | 1,0641,064 |
| Ampacity (30°C ambient) 90°C Wet/Dry | 9595 |
Standards & references
- UL 1569, CSA C22.2 #51
- ICEA S-95-658/NEMA WC-70
- Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
- UL 1685, Two-hour Firewall
- Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
- Sunlight Resistant
- Direct Burial
- Color Code: Black and Numbered
- RoHS Compliant
- NEMA BABA 70901-2-2024 WC-02-03, WC-02-04, WC-02-05
- *U.S. Patent No. 7,309,835