DistributorSouthwire

Service Wire

VFD JACKETED MC (ACWU90) RHW-2/CPE 2,000 Volt Copper

VFD2KGC1/03 VFD JACKETED MC (ACWU90) RHW-2/CPE 2,000 Volt Copper 1/0 AWG

Service Wire #
VFD2KGC1/03

Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RHW-2) , phase identified and cabled together with suitable fillers and three symmetrical bare copper ground conductors. Cable core shielded with 5-mil copper tape, helically applied with 50% overlap for 100% coverage and double tape thickness throughout the cable. Shielded core covered with galvanized steel interlocked armor with overall black CPE jacket. Available with aluminum armor or PVC or EnviroPlus ® (LSZH) jacket. Available with 50% grounds*.

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Application

For use in VFD applications. Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2, Class III - Div 1 and 2 *Patented for use with ServiceDrive ® connector and termination kit.

Specifications

Voltage Rating2 kV (2,000 V)2 kV
CertificationsMade in the USA, REACH, ROHS, Rockwell, ULMade in the USA, REACH, ROHS, Rockwell, UL
Construction1/0 AWG1/0 AWG
Strand1919
Insulation Thickness9595
Grounding Conductors(3) #10(3) #10
Diameter Over Armor1.471.47
Jacket Thickness6060
Approx. Diameter Overall1.571.57
Approx. Net Weight2,0932,093
Ampacity (30°C ambient) 90°C Wet/Dry170170

Standards & references

  • UL 1569, CSA C22.2 #51
  • ICEA S-95-658/NEMA WC-70
  • Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
  • UL 1685, Two-hour Firewall
  • Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
  • Sunlight Resistant
  • Direct Burial
  • Color Code: Black and Numbered
  • RoHS Compliant
  • NEMA BABA 70901-2-2024 WC-02-03, WC-02-04, WC-02-05
  • *U.S. Patent No. 7,309,835