DistributorSouthwire

Service Wire

JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor

Service Wire #
SW-JACKETED-MC-2KV-4-CDRS-GALV

Four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RWU90) , phase identified and cabled together with suitable fillers (when required) and bare copper grounding conductor. Cable core covered with mylar binder tape and galvanized steel interlocked armour, with overall black PVC jacket. Jacket available in colours. Available with ServiceCPE ® jacket.

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (11) ↓

Available sizes & constructions

Size (AWG or Kcmil)(AWG or Kcmil)Strand (no.)(no.)Insulation Thickness (mils)(mm)Grounding Conductor (AWG)(AWG)Diameter Over Armour (in.)(mm)PVC Jacket Thickness (mils)(mm)Approx. Diameter Overall (in.)(mm)Approx. Net Weight (lb./1000')(kg/km)Ampacity (30°C ambient)(30°C ambient)
6677852.16881.0727.2501.271.1729.79241,3757575 GAP2K6/4
4477852.16881.2331.2501.271.3333.81,1951,7789595 GAP2K4/4
2277852.16661.3734.8501.271.4737.31,7372,585130130 GAP2K2/4
11771052.67661.5739.9601.521.6942.92,1523,203145145 GAP2K1/4
1/01/019191052.67661.6742.4601.521.7945.52,5313,767170170 GAP2K1/04
2/02/019191052.67441.7945.5601.521.9148.53,0364,518195195 GAP2K2/04
3/03/019191052.67441.8948.0601.522.0151.13,5545,289225225 GAP2K3/04
4/04/019191052.67442.0351.6601.522.1554.64,2316,296260260 GAP2K4/04
25025037371203.05442.2557.1601.522.3760.25,0907,575290290 GAP2K250/4
35035037371203.05332.5364.3751.912.6868.16,7179,996350350 GAP2K350/4
50050037371203.05222.8572.4751.913.0076.29,00613,402430430 GAP2K500/4

Part numbers in this family (11)

By size:
Southwire #DescriptionConstructionStrandInsulation ThicknessGrounding ConductorDiameter Over ArmourPVC Jacket ThicknessApprox. Diameter OverallApprox. Net WeightAmpacity
GAP2K6/4GAP2K6/4 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 6 AWG 4C6 AWG 4C78581.07501.1792475
GAP2K4/4GAP2K4/4 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 4 AWG 4C4 AWG 4C78581.23501.331,19595
GAP2K2/4GAP2K2/4 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 2 AWG 4C2 AWG 4C78561.37501.471,737130
GAP2K1/4GAP2K1/4 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 1 AWG 4C1 AWG 4C710561.57601.692,152145
GAP2K1/04GAP2K1/04 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 1/0 AWG 4C1/0 AWG 4C1910561.67601.792,531170
GAP2K2/04GAP2K2/04 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 2/0 AWG 4C2/0 AWG 4C1910541.79601.913,036195
GAP2K3/04GAP2K3/04 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 3/0 AWG 4C3/0 AWG 4C1910541.89602.013,554225
GAP2K4/04GAP2K4/04 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 4/0 AWG 4C4/0 AWG 4C1910542.03602.154,231260
GAP2K250/4GAP2K250/4 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 250 kcmil 4C250 kcmil 4C3712042.25602.375,090290
GAP2K350/4GAP2K350/4 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 350 kcmil 4C350 kcmil 4C3712032.53752.686,717350
GAP2K500/4GAP2K500/4 JACKETED MC RWU90/ACW90/ACWU90 1,000/2,000 Volt Copper 4 Conductor 500 kcmil 4C500 kcmil 4C3712022.85753.009,006430

Application & features

Application

Suitable for use in industrial power distribution systems where continuity of service is the prime consideration. May be installed in wet or dry locations, directly buried, or encased in concrete. Suitable for use in cable tray. Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2

Specifications

Voltage Rating2 kV (2,000 V)2 kV
CertificationsCSA, Made in North America, REACH, ROHSCSA, Made in North America, REACH, ROHS

Standards & references

  • UL 44, UL 854, and UL 1569
  • ​​​​​​​CSA C22.2 #51
  • ICEA S-95-658/NEMA WC-70
  • Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU),
  • IEEE 1202/CSA FT-4, Two-hour Firewall
  • Temperature Rated at 90°C Wet/Dry
  • Cold Temperature Rated at -25°C
  • Sunlight and Oil Resistant II Jacket
  • Direct Burial (includes encasement in concrete)
  • Colour Code: Method 4 (optional color codes available)
  • RoHS Compliant