DistributorSouthwire

Southwire

PantoFLEX™ DC Power Cable 2/C CU 1000V XLPE Insulation PVC Jacket. TC-ER XHHW-2 with Green Ground

Southwire #
SPEC48050

Type TC-ER Control Cable 1000 Volt Copper Conductors, Cross-Linked Polyethylene Insulation XHHW-2, Polyvinyl Chloride (PVC) Jacket, Sunlight Resistant - For Direct Burial - Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (3) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)
4/0 AWG4/0 AWG225325320.5301.35551.40802.031.4903.781445215018792796 66591299
250 KCMIL250 KCMIL226276270.6051.54651.65802.031.6664.231713254922113290 66593499
350 KCMIL350 KCMIL228938930.6701.70651.651102.791.8604.722360351230374520 66591499
4/0 AWG4/0 AWG227.519.0533851535.410.0550.080.0670.100.0410.06230230260260 66591299
250 KCMIL250 KCMIL228.321.0840001814.370.0470.070.0570.080.0410.06255255290290 66593499
350 KCMIL350 KCMIL229.323.6256002540.120.0330.050.0420.060.0400.06310310350350 66591499

Part numbers in this family (3)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
665912994/0-532 2/C CU XHHW/PVC BLACK/RED 1x4 GG TYPE TC-ER 1000V BLACK PantoFLEX(TM)4/0 AWG 2C 532SBLACK/REDCUT TO LENGTH REEL
66593499250-627 2/C CU XHHW/PVC BLACK/RED 1x3 GG TYPE TC-ER 1000V BLACK PantoFLEX(TM)250 KCMIL 2C 627SBLACK/REDCUT TO LENGTH REEL
66591499350-893 2/C CU XHHW/PVC BLACK/RED 1x3 GG TYPE TC-ER 1000V BLACK PantoFLEX(TM)350 KCMIL 2C 893SBLACK/REDCUT TO LENGTH REEL

Application & features

Southwire’s 1000 Volt Type TC-ER PantoFLEX™ DC Power Cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC-ER) per NEC 336.10. Silicone free.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Type TC-ER Standard Power and Control Cables (1000V 14AWG and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy