Multi-Conductor Tinned CU Unshielded Signal Cable 1000V
- Southwire #
- SPEC48326
Multi-Conductor Unshielded Signal cables 1000 Volt Single Conductor Tinned Copper, Ethylene Propylene Rubber (EPR) insulation Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket.
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (16) ↓Available sizes & constructions
| Cond. Size | Cond. Strands | Strand Class | Conductor Number | Diameter Over Conductor (in)(cm) | Insulation Thickness (mils)(mm) | Jacket Thickness (mils)(mm) | Approx. OD (inches)(cm) | Approx. Weight (lbs/1000')(kgs/km) | DC Resistance at 25C (ohms/1000')(ohms/km) | Max Pull Tension (lbs)(kg) | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG14 AWG | 1919 | CC | 33 | 0.0740.19 | 802.03 | 802.03 | 0.7081.80 | 222330 | 2.6313.92 | 9844.45 | 45758801 |
| 14 AWG14 AWG | 1919 | CC | 55 | 0.0740.19 | 802.03 | 802.03 | 0.8372.13 | 317472 | 2.6313.92 | 16474.39 | 45759001 |
| 14 AWG14 AWG | 1919 | CC | 77 | 0.0740.19 | 802.03 | 952.41 | 0.9422.39 | 433644 | 2.6313.92 | 230104.33 | 45757201 |
| 12 AWG12 AWG | 1919 | CC | 33 | 0.0900.23 | 802.03 | 802.03 | 0.7421.88 | 258384 | 1.6622.47 | 15670.76 | 45759201 |
| 9 AWG9 AWG | 1919 | CC | 33 | 0.1270.32 | 802.03 | 802.03 | 0.8212.09 | 350521 | 0.8251.23 | 314142.43 | 45759401 |
| 9 AWG9 AWG | 1919 | CC | 44 | 0.1270.32 | 802.03 | 952.41 | 0.9282.36 | 466693 | 0.8251.23 | 418189.60 | 45759601 |
| 9 AWG9 AWG | 1919 | CC | 88 | 0.1270.32 | 802.03 | 952.41 | 1.1933.03 | 8081202 | 0.8251.23 | 837379.66 | 45759801 |
| 6 AWG6 AWG | 1919 | CC | 33 | 0.1790.45 | 952.41 | 952.41 | 1.0352.63 | 593882 | 0.4110.61 | 629285.31 | 45760001 |
Part numbers in this family (16)
By size:
| Southwire # | Description | Construction | Packaging | |
|---|---|---|---|---|
| 14 AWG · 3 conductors (2) | ||||
| 45758899 | 14-19 STR TINNED CU 3/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE | 14 AWG 3C 19 STR | CUT TO LENGTH REEL | |
| 45758801 | 14-19 STR TINNED CU 3/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE 100 | 14 AWG 3C 19 STR | 1000 FT REEL | |
| 14 AWG · 5 conductors (2) | ||||
| 45759099 | 14-19 STR TINNED CU 5/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE | 14 AWG 5C 19 STR | CUT TO LENGTH REEL | |
| 45759001 | 14-19 STR TINNED CU 5/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE 100 | 14 AWG 5C 19 STR | 1000 FT REEL | |
| 14 AWG · 7 conductors (2) | ||||
| 45757299 | 14-19 STR TINNED CU 7/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE | 14 AWG 7C 19S | CUT TO LENGTH REEL | |
| 45757201 | 14-19 STR TINNED CU 7/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE 100 | 14 AWG 7C 19S | 1000 FT REEL | |
| 12 AWG · 3 conductors (2) | ||||
| 45759299 | 12-19 STR TINNED CU 3/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE | 12 AWG 3C 19 STR | CUT TO LENGTH REEL | |
| 45759201 | 12-19 STR TINNED CU 3/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE 100 | 12 AWG 3C 19 STR | 1000 FT REEL | |
| 9 AWG · 3 conductors (2) | ||||
| 45759499 | 9-19 STR TINNED CU 3/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE | 9 AWG 3C 19S | CUT TO LENGTH REEL | |
| 45759401 | 9-19 STR TINNED CU 3/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE 1000 | 9 AWG 3C 19S | 1000 FT REEL | |
| 9 AWG · 4 conductors (2) | ||||
| 45759699 | 9-19 STR TINNED CU 4/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE | 9 AWG 4C 19S | CUT TO LENGTH REEL | |
| 45759601 | 9-19 STR TINNED CU 4/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE 1000 | 9 AWG 4C 19S | 1000 FT REEL | |
| 9 AWG · 8 conductors (2) | ||||
| 45759899 | 9-19 STR TINNED CU 8/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE | 9 AWG 8C 19S | CUT TO LENGTH REEL | |
| 45759801 | 9-19 STR TINNED CU 8/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE 1000 | 9 AWG 8C 19S | 1000 FT REEL | |
| 6 AWG · 3 conductors (2) | ||||
| 45760099 | 6-19 STR TINNED CU 3/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE | 6 AWG 3C 19 STR | CUT TO LENGTH REEL | |
| 45760001 | 6-19 STR TINNED CU 3/C EPR CDR SOLONON JKT BLACK 1000V SIGNAL CABLE 1000 | 6 AWG 3C 19 STR | 1000 FT REEL | |
Application & features
Southwire’s Railroad Signal cables 1000 Volt conform to requirements in AREMA Signal Manual Part 10.3.16 and are suited for use in air or non-plenum ducts.
Standards & references
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy