Southwire

MC-PCS HCF Duo™ Power & Control/Signal Cable 277/480V Colors

Southwire #
SPEC60157

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Interlocked Armor. Signal: 16 AWG Copper TFN insulated singles.

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (13) ↓

Available sizes & constructions

Cond. SizeConductor NumberColorDiameter Over Conductor (in)(cm)Cond. StrandsInsulation Thickness (mils)(mm)Ground SizeDiameter Over Armor (in)(cm)Approx. Weight (lbs/1000')(kgs/km)
12 AWG12 AWG22OE,GYOE,GY0.0800.20SolidSolid200.511x121x120.6321.61164244 59766101
12 AWG12 AWG22BN,GYBN,GY0.0800.201919200.511x121x120.6511.65170253 59767501
12 AWG12 AWG33BN,OE,GYBN,OE,GY0.0800.20SolidSolid200.511x121x120.6741.71193287 59766701
12 AWG12 AWG224.411.181.6622.472.0022.980.0540.0825253030 59766101
12 AWG12 AWG224.611.681.6622.472.0022.980.0540.0825253030 59767501
12 AWG12 AWG334.711.941.6622.472.0022.980.0540.0825253030 59766701

Part numbers in this family (13)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
12 AWG · 2 conductors (12)
5976750112-2 STR CU THHN N/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 250 FT12 AWG 2C 19 STRBRN/GRY/GRN250 FT COIL
5981290112-2 SOL CU THHN N/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 250 FT12 AWG 2C SOLBRN/GRY/GRN250 FT COIL
5976750212-2 STR CU THHN N/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 1000 FT12 AWG 2C 19 STRBRN/GRY/GRN1000 FT REEL
5981290212-2 SOL CU THHN N/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 1000 FT12 AWG 2C SOLBRN/GRY/GRN1000 FT REEL
5981290312-2 SOL CU THHN N/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 1000 FT12 AWG 2C SOLBRN/GRY/GRN1000 FT DRUM
5981290412-2 SOL CU THHN N/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 2500 FT12 AWG 2C SOLBRN/GRY/GRN2500 FT BOX
5976610112-2 SOL CU THHN O/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 250 FT12 AWG 2C SOLORG/GRY/GRN250 FT COIL
5976610212-2 SOL CU THHN O/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 1000 FT12 AWG 2C SOLORG/GRY/GRN1000 FT REEL
6410940212-2 STR CU THHN O/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 1000 FT12 AWG 2C 19 STRORG/GRY/GRN1000 FT REEL
5976630112-2 SOL CU THHN Y/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 250 FT12 AWG 2C SOLYLW/GRY/GRN250 FT COIL
5976630212-2 SOL CU THHN Y/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 1000 FT12 AWG 2C SOLYLW/GRY/GRN1000 FT REEL
6410960212-2 STR CU THHN Y/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BARE AL GRND AIA MCAP-HCF MC-PCS 1000 FT12 AWG 2C 19 STRYLW/GRY/GRN1000 FT REEL
12 AWG · 3 conductors (1)
5976670112-3 SOL CU THHN N/O/A/G 16-2 SOL TFN PR W/ LT BLUE PVC JKT 10 SOL BAREAL GRND AIA MCAP-HCF MC-PCS 250 FT12 AWG 3C SOLBRN/ORG/GRY/GRN250 FT COIL

Application & features

Southwire MC-PCS HCF Duo™ Type MC All Purpose Hospital Care Facility Cable is suitable for use as follows:
• Branch-circuit wiring for patient care areas of hospitals, medical centers, and other health care facilities (when installed in accordance with NEC® Articles 517 and 330, and mechanically protected per Article 300.4). Such areas include nursing homes, dental offices, clinics, and outpatient facilities. Use in hazardous anesthetizing areas is prohibited
• Applications requiring redundant, dedicated or isolated grounding paths
• Fished or embedded in plaster.
• Concealed or exposed installations
• Environmental air-handling spaces per NEC 300.22 (C)
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5
• Power, lighting, control, and signal circuits
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations
• Use with UL Listed MCI-A fittings
• Binder tape with print legend wrapped around assembly
• Type THHN/THWN rated 90ºC dry
• Unjacketed Type MC cables are rated for dry, indoor locations only per NEC 330.10(A)(10)

Southwire MC-PCS HCF Duo™ Type MC Cable meets or exceeds the following requirements:
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
• Federal Specification A-A59544 (formerly J-C-30B)
• NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B800 8000 Series Aluminum Alloy Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.