DistributorSouthwire

Southwire

MC-AP™ HCF Type MC All Purpose Hospital Care Facility THHN/THWN Circuit Size Green Aluminum Armor With Phase ID. Neutral per Phase

Southwire #
SPEC60452

Copper THHN/THWN Insulated Singles. Dedicated Neutral Conductor for Each Phase Conductor. Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Green Aluminum Interlocked Armor. Neutral per Phase

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (3) ↓

Available sizes & constructions

Cond. SizeConductor NumberColorDiameter Over Conductor (in)(cm)Cond. StrandsInsulation Thickness (mils)(mm)Ground SizeNum x Neutral SizeDiameter Over Armor (in)(cm)Approx. Weight (lbs/1000')(kgs/km)
10 AWG10 AWG33See TableSee Table0.1010.26SolidSolid250.641x101x103x103x100.7091.80329490 13937599
10 AWG10 AWG66See TableSee Table0.1010.26SolidSolid250.641x101x106x106x100.9762.48607903 13937399
10 AWG10 AWG99See TableSee Table0.1010.26SolidSolid250.641x101x109x109x101.0682.71637948 13936499
10 AWG10 AWG3330.085.012.701.0401.551.2531.860.0500.0728283232 13937599
10 AWG10 AWG6660.156.817.271.0401.551.2531.860.0500.0717172020 13937399
10 AWG10 AWG9990.237.519.051.0401.551.2531.860.0500.0717172020 13936499
22XXXXXX
44XXXXXXXXXX
66XXXXXXXXXXXXXX
1212XXXXXXXXXXXXXXXXXXXXXXXXXX
1818XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX

Part numbers in this family (3)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
1393759910-3 CU SOL THHN 3X10NEUT PHASE-ID 1X10GG AL GRND MCAP HCF GREEN AIA10 AWG 6C SOL1/1/1/WHT-BLK/WHT-RED/WHT-BLU/GRNCUT TO LENGTH REEL
1393739910-6 CU SOL THHN 6X10NEUT PHASE-ID (2 SETS) 1X10GG AL GRND MCAP HCF GREEN AIA10 AWG 12C1, 1, 1, WT-BK, WT-RD, WT-BU,2, 2, 2, WT-BK, WT-RD, WT-BU,GNCUT TO LENGTH REEL
1393649910-9 CU SOL THHN 9X10NEUT PHASE-ID (3 SETS) 1X10GG AL GRND MCAP HCF GREEN AIA10 AWG 18C1, 1, 1, WT-BK, WT-RD, WT-BU,2, 2, 2, WT-BK, WT-RD, WT-BU,3, 3, 3, WT-BK, WT-RD, WT-BU,GNCUT TO LENGTH REEL

Application & features

MC-AP™ HCF Type MC All Purpose Hospital Care Facility products comply with NEC 200.4 requirements (added in the 2011 NEC) for the installation and marking of neutral conductors. Neutrals are not to be used for more than one circuit (branch, multiwire branch, or ungrounded feeder). See NEC 200.4 for complete requirements.

MC-AP™ HCF Type MC All Purpose Hospital Care Facility is suitable for use as follow:

  • Branch-circuit wiring for patient care areas of hospitals, medical centers, and other health care facilities (when installed in accordance with NEC® Articles 517 and 330, and mechanically protected per Article 300.4). Such areas include nursing homes, dental offices, clinics, and outpatient facilities. Use in hazardous anesthetizing areas is prohibited.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Use with UL Listed MCI-A fittings.
  • Binder tape with print legend wrapped around assembly.
  • Type THHN/THWN rated 90ºC Dry.
  • Neutral per phase
  • Armor is in contact with aluminum grounding/bonding conductor and serves as a redundant equipment grounding path component

  • MC-AP™ HCF Type MC All Purpose Hospital Care Facility meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Standards & references

    • ASTM B3 Soft or Annealed Copper Wire
    • ASTM B8 Concentric-Lay-Stranded Copper Conductors
    • UL 83 Thermoplastic Insulated Wires and Cables
    • UL 1569 Metal-Clad Cables
    • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
    • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
    • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
    • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.