CU FRXLPE LSZH-TP SHIELDED CONTROL CABLE

Southwire #
SUBSTN33

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded SOLONON® Low Smoke Zero Halogen (LSZH) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (10) ↓

Available sizes & constructions

No. of ConductorsSize (AWG or kcmil)(mm2)No. of StrandsInsulation Thickness (mils)(mm)Nom. OD (mils)(mm)Nominal Total Weight (lbs/1000')(kgs/km)
121212 AWG12 AWG77300.7690422.98566842 66250701
2210 AWG10 AWG77300.7658014.74209310 62555401
3310 AWG10 AWG77300.7660815.46259385 66250601
4410 AWG10 AWG77300.7665316.60309460 62556101
7710 AWG10 AWG77300.7675719.24456678 66250401
121210 AWG10 AWG77300.76100425.527561126 62555901

Part numbers in this family (10)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
12 AWG · 12 conductors (1)
6625070112-7 12/C CU XLP E1 CULCT RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATIONWIRE12 AWG 12C 7SBLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK STRIPE/RED-BLACK STRIPE/GREEN-BLACK STRIPE/ORANGE-BLACK STRIPE/BLUE-BLACK STRIPE/BLACK-WHITE STRIPE5000 FT REEL
10 AWG · 2 conductors (3)
6262850110-7 2/C CU XHHW E2 CULCT RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATIONWIRE10 AWG 2C 7 STRBLACK/RED2500 FT REEL
6255540110-7 2/C CU FR-XLPE E1 CULCT RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATION WIRE10 AWG 2C 7 STRBLACK/WHITE2000 FT REEL
6262240110-7 2/C CU FR-XLPE E1 CUHLSHD RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATION WIRE10 AWG 2C 7 STRBLACK/WHITE5000 FT REEL
10 AWG · 3 conductors (1)
6625060110-7 3/C CU FR-XLPE E1 CULCT RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATION WIRE10 AWG 3C 7 STRBLACK/WHITE/RED5000 FT REEL
10 AWG · 4 conductors (2)
6255610110-7 4/C CU FR-XLPE E1 CULCT RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATION WIRE10 AWG 4C 7 STRBLACK/WHITE/RED/GREEN2000 FT REEL
6262230110-7 4/C CU FR-XLPE CUHLSHD RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATION WIRE10 AWG 4C 7 STRBLACK/WHITE/RED/GREEN5000 FT REEL
10 AWG · 7 conductors (1)
6625040110-7 7/C CU FR-XLPE E1 CULCT RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATION WIRE10 AWG 7C 7SBLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK STRIPE5000 FT REEL
10 AWG · 12 conductors (2)
6262220110-7 12/C CU FR-XLPE M1E1 CUHLSHD RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATION WIRE10 AWG 12C 7SBLACK/WHITE/RED/GREEN/BLUE/ORANGE/WHITE-BLACK STRIPE/RED-BLACK STRIPE/GREEN-BLACK STRIPE/ORANGE-BLACK STRIPE/BLUE-BLACK STRIPE/BLACK-WHITE STRIPE2500 FT REEL
6255590110-7 12/C CU FR-XLPE M1E1 CULCT RIP CORD BLACK SOLONON-TP JKT 600V SUBSTATION WIRE10 AWG 12C 7SBLACK/WHITE/RED/GREEN/ORANGE/BLUE/WHITE-BLACK STRIPE/RED-BLACK STRIPE/GREEN-BLACK STRIPE/ORANGE-BLACK STRIPE/BLUE-BLACK STRIPE/BLACK-WHITE STRIPE2000 FT REEL

Application & features

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Only UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Standards & references

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test