DistributorSouthwire

Southwire

CU Compressed 8kV NLEPR Insulation 133% IL SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial

Southwire #
SPEC46271

Type MV-105 Single Conductor Copper, 140 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (5) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Diameter Over Insulation (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Shield (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)Conduit Size (in)(cm)
4/0 AWG4/0 AWG19190.5121.300.8162.071403.560.8762.23802.031.0562.68107816041692767.4812.632.003.07.62 64657399
250 KCMIL250 KCMIL37370.5581.420.8682.201403.560.9282.36802.031.1082.81122718262000907.1813.233.533.58.89 64657699
350 KCMIL350 KCMIL37370.6411.630.9672.461403.561.0272.61802.031.2073.071588236328001270.0614.536.833.58.89 66442999
500 KCMIL500 KCMIL37370.7892.001.0922.771403.561.1522.93802.031.3323.382118315240001814.3715.940.394.010.16 64657999
750 KCMIL750 KCMIL61610.9682.461.3043.311403.561.3643.46802.031.5443.923009447860002721.5518.546.994.511.43 64658099
4/0 AWG4/0 AWG0.0510.080.0650.100.0250.040.0390.060.403 + j0.2750.403 + j0.2750.065 + j0.0470.065 + j0.04727882788295295315315400400445445 64657399
250 KCMIL250 KCMIL0.0430.060.0560.080.0240.040.0380.060.403 + j0.2750.403 + j0.2750.065 + j0.0470.065 + j0.04729552955325325345345445445495495 64657699
350 KCMIL350 KCMIL0.0300.040.0410.060.0220.030.0350.050.570 + j0.4630.570 + j0.4630.204 + j0.0510.204 + j0.05132133213390390415415550550610610 66442999
500 KCMIL500 KCMIL0.0220.030.0300.040.0180.030.0340.050.403 + j0.2750.403 + j0.2750.065 + j0.0470.065 + j0.04736713671465465500500685685765765 64657999
750 KCMIL750 KCMIL0.0140.020.0230.030.0150.020.0320.050.403 + j0.3610.403 + j0.3610.042 + j0.0390.042 + j0.03942574257565565610610885885990990 64658099

Part numbers in this family (5)

By size:
Southwire #DescriptionConstructionPackaging
646573994/0-19 CU 140 MILS NL-EPR 8KV 133% T/S BLACK SIMpull PVC JACKET UL4/0 AWG 1C 19SCUT TO LENGTH REEL
64657699250-37 CU 140 MILS NL-EPR 8KV 133% T/S BLACK SIMpull PVC JACKET UL250 KCMIL 1C 37SCUT TO LENGTH REEL
66442999350-37 CU 140 MILS NL-EPR 8KV 133% T/S BLACK SIMpull PVC JACKET UL350 KCMIL 1C 37SCUT TO LENGTH REEL
64657999500-37 CU 140 MILS NL-EPR 8KV 133% T/S BLACK SIMpull PVC JACKET UL500 KCMIL 1C 37SCUT TO LENGTH REEL
64658099750-61 CU 140 MILS NL-EPR 8KV 133% T/S BLACK SIMpull PVC JACKET UL750 KCMIL 1C 61SCUT TO LENGTH REEL

Application & features

Southwire’s 8KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661