
![]()
1/0-19 CU 90 MILS NL-EPR 5KV 100% T/S BLACK SIMpull PVC JACKET UL
- Southwire #
- 55565699
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications
| Cond. Size | 1/0 AWG1/0 AWG |
|---|---|
| Cond. Strands | 1919 |
| Diameter Over Conductor | 0.361 inch0.92 cm |
| Diameter Over Insulation | 0.580 inch1.47 cm |
| Insulation Thickness | 90 mils2.29 mm |
| Diameter Over Shield | 0.640 inch1.63 cm |
| Jacket Thickness | 55 mils1.40 mm |
| Approx. OD | 0.790 inch2.01 cm |
| Approx. Weight | 578 lbs/1000'860 kgs/km |
| Max Pull Tension | 844 lbs382.83 kg |
| Min. Bend Radius | 9.4 inch23.88 cm |
| Conduit Size | 2.5 inch6.35 cm |
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- UL 1072 Medium-Voltage Power Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661