DistributorSouthwire

Southwire

CU Compressed 5/8kV TRXLPE Insulation 133/100% IL SIM-PVC Jacket. MV 105 - Sunlight Resistant - For Direct Burial

Southwire #
SPEC46106

Type MV-105 Single Conductor Copper, 115 Mils Tree Retardant Cross Linked Polyethylene (TRXLPE) 133% Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Rated UL

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (8) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Diameter Over Insulation (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Shield (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)Conduit Size (in)(cm)
2 AWG2 AWG770.2820.720.5511.401152.920.6111.55551.400.7611.93445662530240.409.123.112.56.35 67373499
1 AWG1 AWG19190.3220.820.5901.501152.920.6501.65551.400.8002.03514765669303.459.624.382.56.35 67335999
1/0 AWG1/0 AWG19190.3610.920.6301.601152.920.6901.75802.030.8702.21623927844382.8310.426.422.56.35 67335699
2/0 AWG2/0 AWG19190.4051.030.6741.711152.920.7341.86802.030.9142.3272710821064482.6210.927.693.07.62 67335399
4/0 AWG4/0 AWG19190.5121.300.7661.951152.920.8262.10802.031.0062.56101115051692767.4812.030.483.07.62 67334699
250 KCMIL250 KCMIL37370.5581.420.8182.081152.920.8782.23802.031.0582.69115517192000907.1812.632.003.07.62 67334299
350 KCMIL350 KCMIL37370.6611.680.9172.331152.920.9772.48802.031.1572.941509224628001270.0613.835.053.58.89 67470399
500 KCMIL500 KCMIL37370.7892.001.0422.651152.921.1022.80802.031.2823.262030302140001814.3715.338.864.010.16 67333999
2 AWG2 AWG0.1620.240.2040.300.0450.070.0440.070.431 + j0.3720.431 + j0.3720.065 + j0.0390.065 + j0.03919201920145145155155190190215215 67373499
1 AWG1 AWG0.1280.190.1620.240.0410.060.0420.060.431 + j0.3720.431 + j0.3720.065 + j0.0390.065 + j0.03920442044170170180180225225250250 67335999
1/0 AWG1/0 AWG0.1020.150.1280.190.0370.060.0420.060.431 + j0.3720.431 + j0.3720.065 + j0.0390.065 + j0.03921652165195195210210260260290290 67335699
2/0 AWG2/0 AWG0.0810.120.1020.150.0340.050.0400.060.431 + j0.3720.431 + j0.3720.065 + j0.0390.065 + j0.03923022302220220235235300300330330 67335399
4/0 AWG4/0 AWG0.0510.080.0650.100.0280.040.0380.060.431 + j0.3720.431 + j0.3720.065 + j0.0390.065 + j0.03926332633290290310310400400445445 67334699
250 KCMIL250 KCMIL0.0430.060.0560.080.0270.040.0370.060.431 + j0.3980.431 + j0.3980.065 + j0.0360.065 + j0.03628002800320320345345445445495495 67334299
350 KCMIL350 KCMIL0.0310.050.0410.060.0230.030.0350.050.431 + j0.4000.431 + j0.4000.065 + j0.0410.065 + j0.04131203120385385415415550550615615 67470399
500 KCMIL500 KCMIL0.0220.030.0300.040.0200.030.0330.050.431 + j0.4420.431 + j0.4420.065 + j0.0380.065 + j0.03835163516470470505505695695775775 67333999

Part numbers in this family (8)

By size:
Southwire #DescriptionConstructionPackaging
673734992-7 CU 115 MILS TR-XLP 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL2 AWG 1C 7SCUT TO LENGTH REEL
673359991-19 CU 115 MILS TR-XLP 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL1 AWG 1C 19SCUT TO LENGTH REEL
673356991/0-19 CU 115 MILS TR-XLP 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL1/0 AWG 1C 19SCUT TO LENGTH REEL
673353992/0-19 CU 115 MILS TR-XLP 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL2/0 AWG 1C 19SCUT TO LENGTH REEL
673346994/0-19 CU 115 MILS TR-XLP 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL4/0 AWG 1C 19SCUT TO LENGTH REEL
67334299250-37 CU 115 MILS TR-XLP 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL250 KCMIL 1C 37SCUT TO LENGTH REEL
67470399350-37 CU 115 MILS TR-XLP 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL350 KCMIL 1C 37SCUT TO LENGTH REEL
67333999500-37 CU 115 MILS TR-XLP 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL500 KCMIL 1C 37SCUT TO LENGTH REEL

Application & features

Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661