2/0-19 3/C CPRESS CU NL-EPR 25% T/S 1X#4 CU GW ARMOR-X MC-HL OR MV-105 25KV 133% ORANGE PVC JACKET
- Southwire #
- 64993899
Type MV-105 Three Conductor Copper, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Continuous Corrugated Welded Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket. Silicone Free
Part of the family: CU Compressed 25kV NLEPR Insulation 133% IL ARMOR-X® Orange PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 25KV ARMOR-X® are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.
Specifications
| Cond. Size | 2/0 AWG2/0 AWG |
|---|---|
| Cond. Strands | 1919 |
| Diameter Over Conductor | 0.405 inch1.03 cm |
| Diameter Over Insulation | 1.084 inch2.75 cm |
| Insulation Thickness | 320 mils8.13 mm |
| Diameter Over Shield | 1.144 inch2.91 cm |
| Ground Size | 1x41x4 |
| Diameter Over Armor | 3.000 inch7.62 cm |
| Jacket Thickness | 75 mils1.91 mm |
| Approx. OD | 3.158 inch8.02 cm |
| Approx. Weight | 4619 lbs/1000'6874 kgs/km |
| Max Pull Tension | 3194 lbs1448.77 kg |
| Min. Bend Radius | 22.0 inch55.88 cm |
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- ASTM B496 Compact Round Concentric-lay-standard copper
- UL 1072 Medium-Voltage Power Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
- ABS Listed as CWCMC