500-37 3/C CU 320 NL-EPR T/S 1X2/0 CU GW AIA ORANGE PVC JACKET 25KV 133% UL
- Southwire #
- 66854499
Type MV-105 Three Conductor Copper, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket. Silicone Free
Part of the family: CU Compressed 25kV NLEPR Insulation 133% IL AIA Orange PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 25KV AIA cables are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501, 502, and 503.
Specifications
| Cond. Size | 500 KCMIL500 KCMIL |
|---|---|
| Cond. Strands | 3737 |
| Diameter Over Conductor | 0.789 inch2.00 cm |
| Diameter Over Insulation | 1.452 inch3.69 cm |
| Insulation Thickness | 320 mils8.13 mm |
| Diameter Over Shield | 1.512 inch3.84 cm |
| Ground Size | 1x2/01x2/0 |
| Diameter Over Armor | 3.637 inch9.24 cm |
| Jacket Thickness | 85 mils2.16 mm |
| Approx. OD | 3.807 inch9.67 cm |
| Approx. Weight | 9330 lbs/1000'13885 kgs/km |
| Max Pull Tension | 12000 lbs5443.10 kg |
| Min. Bend Radius | 26.6 inch67.56 cm |
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- ASTM B496 Compact Round Concentric-lay-standard copper
- UL 1072 Medium-Voltage Power Cables
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661