CU Compressed 2.4kV XLPE Insulation.
- Southwire #
- SPEC46031
Type MV-90 Dry Single Conductor Copper, Non-Shielded Cross Linked Polyethylene (XLPE). Silicone Free
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (4) ↓Available sizes & constructions
| Cond. Size | Cond. Strands | Diameter Over Conductor (in)(cm) | Insulation Thickness (mils)(mm) | Approx. OD (inches)(cm) | Approx. Weight (lbs/1000')(kgs/km) | Max Pull Tension (lbs)(kg) | Min. Bend Radius (in)(cm) | Conduit Size (in)(cm) | |
|---|---|---|---|---|---|---|---|---|---|
| 6 AWG6 AWG | 77 | 0.1740.44 | 1102.79 | 0.4301.09 | 137204 | 21095.25 | 3.48.64 | 1.53.81 | 58468999 |
| 4 AWG4 AWG | 77 | 0.2250.57 | 1102.79 | 0.4811.22 | 215320 | 334151.50 | 3.89.65 | 1.53.81 | 58469099 |
| 2 AWG2 AWG | 77 | 0.2830.72 | 1102.79 | 0.5371.36 | 313466 | 531240.86 | 4.310.92 | 1.53.81 | 58469199 |
| 750 KCMIL750 KCMIL | 6161 | 0.9682.46 | 1353.43 | 1.3003.30 | 25643816 | 60002721.55 | 10.426.42 | 410.16 | 66562799 |
| 6 AWG6 AWG | 0.4110.61 | 0.5150.77 | 0.0420.06 | 8585 | 110110 | 58468999 | |||
| 4 AWG4 AWG | 0.2580.38 | 0.3230.48 | 0.0390.06 | 110110 | 145145 | 58469099 | |||
| 2 AWG2 AWG | 0.1620.24 | 0.2030.30 | 0.0360.05 | 145145 | 190190 | 58469199 | |||
| 750 KCMIL750 KCMIL | 0.1440.21 | 0.0220.03 | 0.0280.04 | 585585 | 900900 | 66562799 |
Part numbers in this family (4)
By size:
| Southwire # | Description | Construction | Packaging | |
|---|---|---|---|---|
| 58468999 | 6-7 CU 110 XLP 2400V N/S DRY LOCATION | 6 AWG 0C 7S | CUT TO LENGTH REEL | |
| 58469099 | 4-7 CU 110 XLP 2400V N/S DRY LOCATION | 4 AWG 0C 7S | CUT TO LENGTH REEL | |
| 58469199 | 2-7 CU 110 XLP 2400V N/S DRY LOCATION | 2 AWG 0C 7S | CUT TO LENGTH REEL | |
| 66562799 | 750-61 CU 130 XLP 2400V N/S DRY LOCATION | 750 KCMIL 0C 61S | CUT TO LENGTH REEL |
Application & features
Southwire’s 2.4KV XLPE cables are suited for use in dry areas, conduits, ducts, troughs, trays and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. Rated for 1000 lbs./FT maximum sidewall pressure. Silicone Free.
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- UL 1072 Medium-Voltage Power Cables
- ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661