DistributorSouthwire

Southwire

2/0-19 CU 125 MILS NL-EPR 2400V N/S WET/DRY PVC JACKET

Southwire #
60723499

Type MV-90 Single Conductor Copper, No Lead Ethylene Propylene Rubber (NL-EPR) Polyvinyl Chloride (PVC) Jacket

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire’s 2.4KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications

Cond. Size2/0 AWG2/0 AWG
Cond. Strands1919
Diameter Over Conductor0.405 inch1.03 cm
Diameter Over Insulation0.695 inch1.77 cm
Insulation Thickness125 mils3.18 mm
Jacket Thickness85 mils2.16 mm
Approx. OD0.871 inch2.21 cm
Approx. Weight671 lbs/1000'999 kgs/km
Max Pull Tension1064 lbs482.62 kg
Min. Bend Radius6.9 inch17.53 cm
Conduit Size2.5 inch6.35 cm

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • CT USE Sizes 1/0 AWG and Larger
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661