DistributorSouthwire

Southwire

CU Compressed 2.4kV NLEPR Insulation 100% IL AIA PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial

Southwire #
SPEC46026

Type MV-105 Three Conductor Copper, 90 Mils Ethylene Propylene Rubber (EPR) Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket. Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (9) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Diameter Over Insulation (in)(cm)Insulation Thickness (mils)(mm)Ground SizeDiameter Over Armor (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)
2 AWG2 AWG770.2820.720.4951.26902.291 x 61 x 61.2833.26551.401.3933.54127819021592722.129.824.89 89008689
1/0 AWG1/0 AWG19190.3610.920.5801.47902.291 x 41 x 41.5673.98651.651.6994.321918285425341149.4011.930.23 60646799
2/0 AWG2/0 AWG19190.4051.030.6251.59902.291 x 41 x 41.6644.23651.651.7964.562258336031941448.7712.632.00 55221299
4/0 AWG4/0 AWG19190.5121.300.7151.82902.291 x 31 x 31.8594.72651.651.9915.063118464050782303.3413.935.31 55221399
350 KCMIL350 KCMIL37370.6611.680.8652.20902.291 x 21 x 22.1835.54802.032.3495.974805715184003810.1716.441.66 55152699
500 KCMIL500 KCMIL37370.7892.000.9902.51902.291 x 11 x 12.4536.23802.032.6196.6564839648120005443.1018.346.48 89064589
750 KCMIL750 KCMIL61610.9682.461.2053.06902.291 x 1/01 x 1/02.9197.41852.163.0897.85923013736180008164.6621.654.86 55225699
2 AWG2 AWG0.1620.240.2040.300.0350.050.186 + j0.020.186 + j0.020.196 + j0.0290.196 + j0.029135135145145140140154154 89008689
1/0 AWG1/0 AWG0.1020.150.1280.190.0320.050.110 + j0.0170.110 + j0.0170.120 + j0.0260.120 + j0.026175175190190185185205205 60646799
2/0 AWG2/0 AWG0.0810.120.1020.150.0320.050.084 + j0.0160.084 + j0.0160.094 + j0.0250.094 + j0.025200200220220215215240240 55221299
4/0 AWG4/0 AWG0.0510.080.0650.100.0300.040.047 + j0.0150.047 + j0.0150.057 + j0.0230.057 + j0.023265265280280285285320320 55221399
350 KCMIL350 KCMIL0.0310.050.0410.060.0280.040.023 + j0.0130.023 + j0.0130.033 + j0.0220.033 + j0.022355355380380395395440440 55152699
500 KCMIL500 KCMIL0.0220.030.0300.040.0270.040.012 + j0.0120.012 + j0.0120.022 + j0.0210.022 + j0.021430430460460485485545545 89064589
750 KCMIL750 KCMIL0.0140.020.0230.030.0270.040.005 + j0.0110.005 + j0.0110.015 + j0.020.015 + j0.02530530570570615615685685 55225699

Part numbers in this family (9)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
2 AWG (2)
890086992-7 CU 3C 90 MILS NL-EPR1X6 CU GW AIA PVC 2400V N/S2 AWG 3C 7 STRBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-CUT TO LENGTH REEL
890086892-7 CU 3C 90 MILS NL-EPR1X6 CU GW AIA PVC 2400V N/S 3100 FT2 AWG 3C 7 STRBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-3100 FT REEL
1/0 AWG (1)
606467991/0-19 CU 3C 90 MILS NL-EPR1X4 CU GW AIA PVC 2400V N/S1/0 AWG 3C 19 STRBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-CUT TO LENGTH REEL
2/0 AWG (1)
552212992/0-19 CU 3C 90 MILS NL-EPR1X4 CU GW AIA PVC 2400V N/S2/0 AWG 3C 19 STRBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-CUT TO LENGTH REEL
4/0 AWG (1)
552213994/0-19 CU 3C 90 MILS NL-EPR1X3 CU GW AIA PVC 2400V N/S4/0 AWG 3C 19 STRBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-CUT TO LENGTH REEL
350 kcmil (1)
55152699350-37 CU 3C 90 MILS NL-EPR1X2 CU GW AIA PVC 2400V N/S350 KCMIL 3C 37 STRBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-CUT TO LENGTH REEL
500 kcmil (2)
89064599500-37 CU 3C 90 MILS NL-EPR1X1 CU GW AIA PVC 2400V N/S500 KCMIL 3C 37SBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-CUT TO LENGTH REEL
89064589500-37 CU 3C 90 MILS NL-EPR1X1 CU GW AIA PVC 2400V N/S 2100 FT500 KCMIL 3C 37SBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-2100 FT REEL
750 kcmil (1)
55225699750-61 CU 3C 90 MILS NL-EPR1X1/0 CU GW AIA PVC 2400V N/S750 KCMIL 3C 61SBLACK/NATURAL-/BLACK/NATURAL-/BLACK/NATURAL-/-CUT TO LENGTH REEL

Application & features

Southwire’s 2.4KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed or dual UL/CSA listed. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661