CU 600V XLPE Insulation ARMOR-X® SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket XHHW-2 VFD Cable. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Southwire #
SPEC45228

Type MC-HL Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Continuous Corrugated Welded Armor - ARMOR-X®, Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket with 3 Bare CU Ground

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (2) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsInsulation Thickness (mils)(mm)Diameter Over Armor (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)DC Resistance at 25C (ohms/1000')(ohms/km)AC Resistance at 75C (ohms/1000')(ohms/km)Min. Bend Radius (in)(cm)Allowable Ampacity Raceway 75CAllowable Ampacity Raceway 90C
12 AWG12 AWG3377300.760.5701.45501.270.6701.70851262333471.6622.472.0022.984.711.9425253030 64146899
10 AWG10 AWG3377300.760.6101.55501.270.7161.821352012994451.0401.551.2531.865.012.7035354040 64150499

Part numbers in this family (2)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
6414689912-7 3/C CPRESS CU XHHW-2 3X#16 CU GW ARMOR-X MC-HL 600V BLACK SOLONON JACKET12 AWG 3C 7SBLACK-1-ONE/RED-2-TWO/BLUE-3-THREE/16 AWG BARE GRND/16 AWG BARE GRND/16 AWG BARE GRNDCUT TO LENGTH REEL
6415049910-7 3/C CPRESS CU XHHW-2 3X#14 CU GW ARMOR-X MC-HL 600V BLACK SOLONON JACKET10 AWG 3C 7 STRBLACK-1-ONE/RED-2-TWO/BLUE-3-THREE/14 AWG BARE GRND/14 AWG BARE GRND/14 AWG BARE GRNDCUT TO LENGTH REEL

Application & features

Southwire's 600 Volt Type MC-HL ARMOR-X® control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1309 Marine Shipboard Cable
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)