CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2 Shielded. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Southwire #
SPEC45158

Type TC-ER, PLTC, FPL, and NFPL Control Cable 600 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation THHN/THWN Polyvinyl Chloride (PVC) Jacket, Shielded Control Cable Conductor Identification Method 1 Table 2

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (5) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsInsulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)DC Resistance at 25C (ohms/1000')(ohms/km)AC Resistance at 75C (ohms/1000')(ohms/km)Min. Bend Radius (in)(cm)Allowable Ampacity Raceway 75CAllowable Ampacity Raceway 90C
14 AWG14 AWG2277150.38451.140.3230.82334966982.6313.923.1704.721.33.3020202525 58127602
12 AWG12 AWG4477150.38451.140.4221.07931381482201.6622.472.0022.981.74.3220202424 58160002

Part numbers in this family (5)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
14 AWG · 2 conductors (3)
5812769914-7 2/C CU THHN/PVC BLACK/RED TYPE TC/PLTC OAS BLACK14 AWG 2C 7 STRBLACK/REDCUT TO LENGTH REEL
5812760314-7 2/C CU THHN/PVC BLACK/RED TYPE TC/PLTC OAS BLACK 2500 FT14 AWG 2C 7 STRBLACK/RED2500 FT REEL
5812760214-7 2/C CU THHN/PVC TYPE TC 600V BLACK 1000 FT14 AWG 2C 7 STRnull1000 FT REEL
12 AWG · 4 conductors (2)
5816009912-7 4/C CU THHN/PVC BLACK/RED/BLUE/ORANGE TYPE TC-ER/PLTC BLACK12 AWG 4C 7 STRBLACK/RED/BLUE/ORANGECUT TO LENGTH REEL
5816000212-7 4/C CU THHN/PVC BLACK/RED/BLUE/ORANGE TYPE TC-ER/PLTC BLACK 1000 FT12 AWG 4C 7 STRBLACK/RED/BLUE/ORANGE1000 FT REEL

Application & features

Southwire’s Type TC-ER, PLTC, FPL, and NFPL Control Cable are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in dry locations and 75°C in wet locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III per NEC Article 725 and 760. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Oil and sunlight resistant.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 13 Power-Limited Circuit Cables
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 TC-ER
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • EPA 40 CFR, Part 26, Subpart C heavy metals per Table 1, TCLP method