DistributorSouthwire

Southwire

14 SOL CU 4/C THHN/PVC MINISPLIT TYPE TC 600V BLACK 50 FT

Southwire #
59540702

CU 600V PVC Insulation PVC Jacket Mini Split Type THHN/THWN Rated at 75ºC Wet 90ºC Dry

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire’s 600 Volt Type TC-ER-JP control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free - VW-1 Rated.

Specifications

Cond. Size14 AWG14 AWG
Conductor Number44
Cond. Strands11
Diameter Over Conductor0.064 inch0.16 cm
ColorBK, RD, WE, GNBK, RD, WE, GN
Insulation Thickness20 mils0.51 mm
Jacket Thickness45 mils1.14 mm
Approx. OD0.348 inch0.88 cm
Copper Weight50 lbs/1000'74 kgs/km
Approx. Weight89 lbs/1000'132 kgs/km
DC Resistance at 25C2.631 ohms/1000'3.92 ohms/km
AC Resistance at 75C3.170 ohms/1000'4.72 ohms/km
Min. Bend Radius1.4 inch3.56 cm
Allowable Ampacity Raceway 75C1616
Allowable Ampacity Raceway 90C2020

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wire and Cables (sizes 14 AWG to 1000 kcmil)
  • UL 1277 Electrical Power and Control Tray Cables
  • RoHS-3 Complies with European Directive 2015/863