DistributorSouthwire

Southwire

CU 600/1000V XLPE Insulation Thermoplastic LSZH-TP XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Southwire #
SPEC45254

Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (8) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)
8 AWG8 AWG33770.1410.36451.14601.520.7101.80186277340506 56156899
6 AWG6 AWG33770.1770.45451.14601.520.7952.02297442480714 56156799
2 AWG2 AWG33770.2820.72451.14802.030.9802.4970210459791457 55137899
2/0 AWG2/0 AWG3319190.4051.03551.40802.031.3023.311326197317192558 56156499
3/0 AWG3/0 AWG3319190.4561.16551.40802.031.4063.571699252821323173 56581599
4/0 AWG4/0 AWG3319190.5121.30551.40802.031.5313.892109313926153892 95971899
500 KCMIL500 KCMIL3337370.7892.00651.651102.792.2335.674923732659658877 55236299
8 AWG8 AWG332.87.11396179.620.6530.970.7861.170.0520.0850505555 56156899
6 AWG6 AWG333.28.13629285.310.4110.610.4950.740.0510.0865657575 56156799
2 AWG2 AWG333.99.911592722.120.1620.240.1950.290.0450.07115115130130 55137899
2/0 AWG2/0 AWG336.516.5131941448.770.0810.120.0970.140.0430.06175175195195 56156499
3/0 AWG3/0 AWG337.017.7840271826.610.0640.100.0780.120.0420.06200200225225 56581599
4/0 AWG4/0 AWG337.719.5650782303.340.0510.080.0620.090.0410.06230230260260 95971899
500 KCMIL500 KCMIL3313.434.04120005443.100.0220.030.0290.040.0390.06380380430430 55236299

Part numbers in this family (8)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
8 AWG (1)
561568998-7 3/C CU XHHW/SOLONON PHASE ID 1X#10 GG TYPE TC-ER 600V BLACK8 AWG 3C 7 STR1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
6 AWG (1)
561567996-7 3/C CU XHHW/SOLONON PHASE ID 1X#8 GG TYPE TC-ER 600V BLACK6 AWG 3C 7 STR1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
2 AWG (1)
551378992-7 3/C CU XHHW/SOLONON PHASE ID 1X#6 GW TYPE TC-ER 600V BLACK2 AWG 3C 7 STR1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
2/0 AWG (1)
561564992/0-19 3/C CU XHHW/SOLONON PHASE ID 1X#6 GW TYPE TC-ER 600V BLACK2/0 AWG 3C 19 STR1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
3/0 AWG (1)
565815993/0-19 3/C CU XHHW/SOLONON PHASE ID 1X#4 GW TYPE TC-ER 600V BLACK3/0 AWG 3C 19 STR1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
4/0 AWG (1)
959718994/0-19 3/C TINNED CU XHHW/XLP PHASE ID 1X#4 GW TYPE TC-ER 600V BLACK4/0 AWG 3C 19 STR1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
500 kcmil (2)
55236299500-37 3/C TINNED CU XHHW/SOLONON PHASE ID 3X#6 GW TYPE TC-ER 600V BLACK500 KCMIL 3C 37S1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
56493899500-37 3/C CU XHHW/SOLONON PHASE ID 1X#2 GW TYPE TC-ER 600V BLACK500 KCMIL 3C 37S1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL

Application & features

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)