CU 600/1000V XLPE Insulation PVC Jacket XHHW-2 With Green Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
- Southwire #
- SPEC45103
Type TC-ER Control Cable 600 or 1000 Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Insulated Green CU Ground, Control Cable Conductor Identification Method 1 Table 2. Silicone Free
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (8) ↓Available sizes & constructions
| Cond. Size | Conductor Number | Cond. Strands | Color | Insulation Thickness (mils)(mm) | Jacket Thickness (mils)(mm) | Approx. OD (inches)(cm) | Copper Weight (lbs/1000')(kgs/km) | Approx. Weight (lbs/1000')(kgs/km) | DC Resistance at 25C (ohms/1000')(ohms/km) | AC Resistance at 75C (ohms/1000')(ohms/km) | Min. Bend Radius (in)(cm) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG14 AWG | 33 | 77 | BK,RD,BE,GNBK,RD,BE,GN | 300.76 | 451.14 | 0.4091.04 | 5176 | 110164 | 2.6313.92 | 3.1704.72 | 1.64.06 | 2020 | 2525 | 95583199 |
| 12 AWG12 AWG | 22 | 77 | BK,RD,GNBK,RD,GN | 300.76 | 451.14 | 0.4251.08 | 6191 | 122182 | 1.6622.47 | 2.0022.98 | 1.74.32 | 2525 | 3030 | 45756299 |
| 12 AWG12 AWG | 33 | 77 | BK,RD,BE,GNBK,RD,BE,GN | 300.76 | 451.14 | 0.4491.14 | 81121 | 152226 | 1.6622.47 | 2.0022.98 | 1.84.57 | 2525 | 3030 | 95593099 |
| 12 AWG12 AWG | 44 | 77 | BK,RD,BE,OE,GNBK,RD,BE,OE,GN | 300.76 | 451.14 | 0.4911.25 | 101150 | 176262 | 1.6622.47 | 2.0022.98 | 2.05.08 | 2020 | 2424 | 95594899 |
| 10 AWG10 AWG | 22 | 77 | BK,RD,GNBK,RD,GN | 300.76 | 451.14 | 0.4761.21 | 97144 | 168250 | 1.0401.55 | 1.2531.86 | 1.94.83 | 3535 | 4040 | 45756499 |
| 10 AWG10 AWG | 33 | 77 | BK,RD,BE,GNBK,RD,BE,GN | 300.76 | 451.14 | 0.5471.39 | 129192 | 224333 | 1.0401.55 | 1.2531.86 | 2.25.59 | 3535 | 4040 | 95595599 |
| 10 AWG10 AWG | 44 | 77 | BK,RD,BE,OE,GNBK,RD,BE,OE,GN | 300.76 | 601.52 | 0.6031.53 | 161240 | 273406 | 1.0401.55 | 1.2531.86 | 2.46.10 | 2828 | 3232 | 95596399 |
| 10 AWG10 AWG | 55 | 77 | BK,RD,BE,OE,YW,GNBK,RD,BE,OE,YW,GN | 300.76 | 601.52 | 0.6571.67 | 193287 | 322479 | 1.0401.55 | 1.2531.86 | 2.66.60 | 2828 | 3232 | 66604199 |
Part numbers in this family (8)
| Southwire # | Description | Construction | Conductor Color | Packaging | |
|---|---|---|---|---|---|
| 95583199 | 14-7 3/C CU XHHW/PVC PHASE ID 1x14 GG TYPE TC-ER 1000V BLACK | 14 AWG 3C 7 STR | BLACK/RED/BLUE | CUT TO LENGTH REEL | |
| 45756299 | 12-7 2/C CU XHHW/PVC BLACK/RED 1x12 GG TYPE TC-ER 1000V BLACK | 12 AWG 2C 7 STR | BLACK/RED | CUT TO LENGTH REEL | |
| 95593099 | 12-7 3/C CU XHHW/PVC PHASE ID 1x12 GG TYPE TC-ER 1000V BLACK | 12 AWG 3C 7S | BLACK/RED/BLUE | CUT TO LENGTH REEL | |
| 95594899 | 12-7 4/C CU XHHW/PVC PHASE ID 1x12 GG TYPE TC-ER 1000V BLACK | 12 AWG 4C 7 STR | BLACK/RED/BLUE/ORANGE | CUT TO LENGTH REEL | |
| 45756499 | 10-7 2/C CU XHHW/PVC BLACK/RED 1x10 GG TYPE TC-ER 1000V BLACK | 10 AWG 2C 7 STR | BLACK/RED | CUT TO LENGTH REEL | |
| 95595599 | 10-7 3/C CU XHHW/PVC PHASE ID 1x10 GG TYPE TC-ER 1000V BLACK | 10 AWG 3C 7 STR | BLACK/RED/BLUE | CUT TO LENGTH REEL | |
| 95596399 | 10-7 4/C CU XHHW/PVC PHASE ID 1x10 GG TYPE TC-ER 1000V BLACK | 10 AWG 4C 7 STR | BLACK/RED/BLUE/ORANGE | CUT TO LENGTH REEL | |
| 66604199 | 10-7 5/C CU XHHW/PVC PHASE ID 1x10 GG TYPE TC-ER 1000V BLACK | 10 AWG 5C 7S | BLACK/RED/BLUE/ORANGE/YELLOW | CUT TO LENGTH REEL |
Application & features
Southwire’s 600 or 1000 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone Free
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1277 Electrical Power and Control Tray Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
- ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- VW-1 (Vertical-Wire) Flame Test