CU 600/1000V XLPE Insulation PVC Jacket XHHW-2 with Bare or Green Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
- Southwire #
- SPEC45240
Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare or Green Insulated Ground. Silicone Free.
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (3) ↓Available sizes & constructions
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in)(cm) | Insulation Thickness (mils)(mm) | Jacket Thickness (mils)(mm) | Approx. OD (inches)(cm) | Copper Weight (lbs/1000')(kgs/km) | Approx. Weight (lbs/1000')(kgs/km) | |
|---|---|---|---|---|---|---|---|---|---|
| 8 AWG8 AWG | 22 | 77 | 0.1410.36 | 451.14 | 601.52 | 0.5921.50 | 135201 | 242360 | 67104299 |
| 6 AWG6 AWG | 22 | 77 | 0.1770.45 | 451.14 | 601.52 | 0.6911.76 | 215320 | 341507 | 57095999 |
| 4 AWG4 AWG | 22 | 77 | 0.2250.57 | 451.14 | 601.52 | 0.7481.90 | 311463 | 444661 | 59624099 |
| 8 AWG8 AWG | 22 | 2.46.10 | 264119.75 | 0.6530.97 | 0.7861.17 | 0.0520.08 | 5050 | 5555 | 67104299 |
| 6 AWG6 AWG | 22 | 2.87.11 | 419190.06 | 0.4110.61 | 0.4950.74 | 0.0510.08 | 6565 | 7575 | 57095999 |
| 4 AWG4 AWG | 22 | 3.07.62 | 667302.55 | 0.2580.38 | 0.3100.46 | 0.0480.07 | 8585 | 9595 | 59624099 |
Part numbers in this family (3)
| Southwire # | Description | Construction | Conductor Color | Packaging | |
|---|---|---|---|---|---|
| 67104299 | 8-7 2/C CU XHHW/PVC PHASE ID 1x10 GG TYPE TC-ER 600V BLACK | 8 AWG 2C 7 STR | BLACK/BLACK | CUT TO LENGTH REEL | |
| 57095999 | 6-7 2/C CU XHHW/PVC PHASE ID 1x8 GG TYPE TC-ER 1000V BLACK | 6 AWG 2C 7 STR | 1-BLACK/2-RED | CUT TO LENGTH REEL | |
| 59624099 | 4-7 2/C CU XHHW-2/PVC PHASE ID 1x8 GW TYPE TC-ER 1000V BLACK | 4 AWG 2C 7 STR | 1-BLACK/2-RED | CUT TO LENGTH REEL |
Application & features
Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC-ER) per NEC 336.10. Silicone free.
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1277 Electrical Power and Control Tray Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- IEEE 383 Flame Test (70,000 btu)
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test