DistributorSouthwire

Southwire

CU 600/1000V XLPE Insulation ARMOR-X® Thermoplastic LSZH-TP Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Southwire #
SPEC45354

Type MC-HL Power Cable 600 or 1000 Volt Four Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation Type XHHW-2, Continuous Corrugated Welded Armor - ARMOR-X®, Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket with 1 Bare Copper Ground

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (4) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Armor (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)
4 AWG4 AWG770.2250.57451.141.0202.59501.271.1202.8491413601068484.447.819.81 64152099
2/0 AWG2/0 AWG19190.4051.03551.401.5403.91601.521.6604.222444363734071545.3911.629.46 57242199
4/0 AWG4/0 AWG19190.5121.30551.401.8454.69601.521.9654.993541527054162456.6513.835.05 55085699
500 KCMIL500 KCMIL37370.7892.00651.652.6706.78751.912.8207.16775611542128005805.9819.750.04 56306999
4 AWG4 AWG0.2580.380.3100.460.0220.030.0480.07 64152099
2/0 AWG2/0 AWG0.0810.120.0970.140.0160.020.0430.06 57242199
4/0 AWG4/0 AWG0.0510.080.0620.090.0130.020.0410.06 55085699
500 KCMIL500 KCMIL0.0220.030.0290.040.0100.010.0390.06 56306999

Part numbers in this family (4)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
641520994-7 4/C CPRESS CU XHHW-2 1X#8 CU GW ARMOR-X MC-HL 600V BLACK SOLONON JACKET4 AWG 4C 7 STR1-BLACK/2-RED/3-BLUE/4-ORANGE/8 AWG BARE GRNDCUT TO LENGTH REEL
572421992/0-19 4/C CPRESS CU XHHW-2 1X#4 CU GW ARMOR-X MC-HL 600V BLACK SOLONONJACKET2/0 AWG 4C 19 STR1-BLACK/2-RED/3-BLUE/4-ORANGE/4 AWG BARE GRNDCUT TO LENGTH REEL
550856994/0-19 4/C CPRESS CU XHHW-2 1X#4 CU GW ARMOR-X MC-HL 600V BLACK SOLONONJACKET4/0 AWG 4C 19 STR1-BLACK/2-RED/3-BLUE/4-ORANGE/4 AWG BARE GRNDCUT TO LENGTH REEL
56306999500-37 4/C CPRESS CU XHHW-2 1X#2 CU GW ARMOR-X MC 600V BLACK SOLONON JACKET500 KCMIL 4C 37S1-BLACK/2-RED/3-BLUE/4-ORANGE/2 AWG BARE GRNDCUT TO LENGTH REEL

Application & features

Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -40°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)