DistributorSouthwire

Southwire

CU 2400V NL-EPR Thermoset SOLONON LSZH-TS TRACTION POWER CABLE. MV 90

Southwire #
SPEC48204

Traction Power Cable 2400 Volt Single Conductor Copper, No Lead Ethylene Propylene Rubber (NL-EPR) insulation Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (9) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)
1/0 AWG1/0 AWG19190.3610.921253.18802.030.8262.10568845845383.29 13899499
2/0 AWG2/0 AWG19190.4051.031253.18802.030.8712.216719991065483.08 13899599
3/0 AWG3/0 AWG19190.4561.161253.18952.410.9552.4383012351342608.72 13899699
4/0 AWG4/0 AWG19190.5121.301253.18952.410.9952.5397814551693767.93 13899799
250 KCMIL250 KCMIL37370.5581.421403.561102.791.1122.82117917552000907.18 13899899
350 KCMIL350 KCMIL37370.6611.681403.561102.791.2073.071531227828001270.06 13899999
500 KCMIL500 KCMIL37370.7892.001403.561102.791.3223.362039303440001814.37 13900099
750 KCMIL750 KCMIL61610.9682.461553.941253.181.6114.093038452160002721.55 13900199
1000 KCMIL1000 KCMIL61611.1172.841553.941253.181.7614.473893579380003628.74 13900299
1/0 AWG1/0 AWG 13899499
2/0 AWG2/0 AWG 13899599
3/0 AWG3/0 AWG 13899699
4/0 AWG4/0 AWG 13899799
250 KCMIL250 KCMIL 13899899
350 KCMIL350 KCMIL 13899999
500 KCMIL500 KCMIL 13900099
750 KCMIL750 KCMIL 13900199
1000 KCMIL1000 KCMIL 13900299

Part numbers in this family (9)

By size:
Southwire #DescriptionConstructionPackaging
138994991/0-19 CU 125 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)1/0 AWG 1C 19SCUT TO LENGTH REEL
138995992/0-19 CU 125 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)2/0 AWG 1C 19SCUT TO LENGTH REEL
138996993/0-19 CU 125 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)3/0 AWG 1C 19SCUT TO LENGTH REEL
138997994/0-19 CU 125 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)4/0 AWG 1C 19SCUT TO LENGTH REEL
13899899250-37 CU 140 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)250 KCMIL 1C 37SCUT TO LENGTH REEL
13899999350-37 CU 140 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)350 KCMIL 1C 37SCUT TO LENGTH REEL
13900099500-37 CU 140 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)500 KCMIL 1C 37SCUT TO LENGTH REEL
13900199750-61 CU 155 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)750 KCMIL 1C 61SCUT TO LENGTH REEL
139002991000-61 CU 155 MILS NL-EPR 2400V N/S WET/DRY SOLONON-TS JACKET (5kV NON-UL)1000 KCMIL 1C 61SCUT TO LENGTH REEL

Application & features

Southwire 2400V No Lead NL-EPR/SOLONON Traction Power Cable is suited for use in mass transit and general industry applications where flexibility, fire resistance, and low smoke generation are a concern. May be installed in wet or dry locations in cable trays or raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Resistance to moisture and most oils, acids, and alkalis with an overall durable LSZH XLPO jacket. Meets Flame Spread and Smoke Release requirements of NFPA 130. Rated for 1000 lb/ft maximum sidewall pressure.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (1/0 AWG and larger)
  • AREMA 10.3.13 Recommended Design Criteria for Low-Smoke Halogen Free (LSHF) Polymeric Cable Jackets