2/0-12 3/C 3E AL 220 NL-EPR T/S 1X4 CU GW AIA RED PVC JACKET 15KV 133%UL
- Southwire #
- 59778199
Type MV-105 Three Conductor Aluminum, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket. Silicone Free
Part of the family: AL Compact 15kV NLEPR Insulation 133% IL AIA Red PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed or dual UL/CSA listed. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications
| Cond. Size | 2/0 AWG2/0 AWG |
|---|---|
| Cond. Strands | 1212 |
| Diameter Over Conductor | 0.376 inch0.96 cm |
| Diameter Over Insulation | 0.854 inch2.17 cm |
| Insulation Thickness | 220 mils5.59 mm |
| Diameter Over Shield | 0.914 inch2.32 cm |
| Ground Size | 1x41x4 |
| Diameter Over Armor | 2.345 inch5.96 cm |
| Jacket Thickness | 80 mils2.03 mm |
| Approx. OD | 2.511 inch6.38 cm |
| Approx. Weight | 2620 lbs/1000'3899 kgs/km |
| Max Pull Tension | 2395 lbs1086.35 kg |
| Min. Bend Radius | 17.5 inch44.45 cm |
Standards & references
- ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
- ASTM B836 Compact Rounded Stranded Aluminum Conductors
- UL 1072 Medium-Voltage Power Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661