600V CU PVC-Nylon/PVC Pairs POS
- Southwire #
- SPEC43602
Type TC Instrumentation Cable 600 Volt Copper Conductors PVC/Nylon Insulated Singles with Overall Shield POS. PVC Jacket Heat, Moisture, Oil and Sunlight Resistant RoHS rated for -25°C to 90°C
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (10) ↓Available sizes & constructions
| Cond. Size | Conductor Number | Diameter Over Conductor (in)(cm) | Insulation Thickness (mils)(mm) | Jacket Thickness (mils)(mm) | Approx. OD (inches)(cm) | Approx. Weight (lbs/1000')(kgs/km) | Min. Bend Radius (in)(cm) | DC Resistance at 25C (ohms/1000')(ohms/km) | |
|---|---|---|---|---|---|---|---|---|---|
| 18 AWG18 AWG | 11 | 0.0450.11 | 150.38 | 451.14 | 0.2640.67 | 3857 | 1.53.81 | 6.6699.92 | 56295101 |
| 16 AWG16 AWG | 11 | 0.0560.14 | 150.38 | 451.14 | 0.2920.74 | 4973 | 1.74.32 | 4.1816.22 | 56295402 |
| 16 AWG16 AWG | 22 | 0.0560.14 | 150.38 | 451.14 | 0.4231.07 | 86128 | 2.56.35 | 4.1816.22 | 58137602 |
| 16 AWG16 AWG | 1212 | 0.0560.14 | 150.38 | 802.03 | 0.8292.11 | 400595 | 4.912.45 | 4.1816.22 | 58142402 |
| 1818 | 40.6640.66 | 0.09570.0957 | |||||||
| 1616 | 48.5148.51 | 0.08950.0895 |
Part numbers in this family (10)
| Southwire # | Description | Construction | Conductor Color | Packaging | |
|---|---|---|---|---|---|
| 18 AWG · 2 conductors (2) | |||||
| 56295199 | 18/1 PAIR STR CU TFN/PVC OAS TYPE TC BLACK | 18 AWG 2C 7 STR | BLACK/WHITE | CUT TO LENGTH REEL | |
| 56295101 | 18/1 PAIR STR CU TFN/PVC OAS TYPE TC BLACK 10000 FT | 18 AWG 2C 7 STR | BLACK/WHITE | 10000 FT REEL | |
| 16 AWG · 2 conductors (4) | |||||
| 56295499 | 16/1 PAIR STR CU TFN/PVC OAS TYPE TC BLACK | 16 AWG 2C 7 STR | BLACK/WHITE | CUT TO LENGTH REEL | |
| 56295402 | 16/1 PAIR STR CU TFN/PVC OAS TYPE TC BLACK 1000 FT | 16 AWG 2C 7 STR | BLACK/WHITE | 1000 FT REEL | |
| 56295425 | 16/1 PAIR STR CU TFN/PVC OAS TYPE TC BLACK 2500 FT | 16 AWG 2C 7 STR | BLACK/WHITE | 2500 FT REEL | |
| 56295426 | 16/1 PAIR STR CU TFN/PVC OAS TYPE TC BLACK 2500 FT | 16 AWG 2C 7 STR | BLACK/WHITE | 2500 FT REEL | |
| 16 AWG · 4 conductors (2) | |||||
| 58137699 | 16/2 PAIR STR CU TFN/PVC TYPE TC-ER BLACK | 16 AWG 4C 7 STR | CUT TO LENGTH REEL | ||
| 58137602 | 16/2 PAIR STR CU TFN/PVC TYPE TC-ER BLACK 2000 FT | 16 AWG 4C 7 STR | 2000 FT REEL | ||
| 16 AWG · 24 conductors (2) | |||||
| 58142499 | 16/12 PAIR STR CU TFN/PVC TYPE TC-ER BLACK | 16 AWG 24C 7S | CUT TO LENGTH REEL | ||
| 58142402 | 16/12 PAIR STR CU TFN/PVC TYPE TC-ER BLACK 2000 FT | 16 AWG 24C 7S | 2000 FT REEL | ||
Application & features
Southwire’s Instrumentation Cables Type TC UL 1277 are suitable for installations as outlined in NEC Article 336 for process control and instrumentation, control circuits for operation and interconnection of protective and signaling devices and for general use in manufacturing, industrial and commercial distribution systems. Cables are constructed with 7-strand copper conductors insulated with nylon covered PVC. The paired conductors are colored black, white, and alpha-numeric printed. The overall assembly is covered with an aluminum polyester foil with 100% coverage and a tinned drain wire. The cable is suited for use in cable trays, raceways, conduit, aerial (when supported with a messenger) and direct burial. The cable is rated for -25°C to 90°C and rated for Class I Div II hazardous locations, sun and oil resistant. The jacket is black PVC with a nylon ripcord for easy removal. 1 Pair is not TC-ER Rated.
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 66 Fixture Wire Type TFN
- UL 1277 Electrical Power and Control Tray Cables
- IEEE 383 Flame Test (70,000 btu)
- EPA 40 CFR, Part 26, Subpart C heavy metals per Table 1, TCLP method
- RoHS-2 (European Directive 2011/65/EU)
- NEC Article 336 Power and Control Tray Cable