600V CU EPR PAIRS CPE POS Instrumentation
- Southwire #
- SPEC43618
Type TC-ER Instrumentation Cable 600 Volt Tinned Copper Conductors EPR Insulated Single Pairs with Overall Shield POS. CPE Jacket Heat, Moisture, Oil and Sunlight Resistant. Rated for -30°C to 90°C
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (2) ↓Available sizes & constructions
| Cond. Size | Conductor Number | Diameter Over Conductor (in)(cm) | Insulation Thickness (mils)(mm) | Jacket Thickness (mils)(mm) | Approx. OD (inches)(cm) | Approx. Weight (lbs/1000')(kgs/km) | Min. Bend Radius (in)(cm) | DC Resistance at 25C (ohms/1000')(ohms/km) | |
|---|---|---|---|---|---|---|---|---|---|
| 16 AWG16 AWG | 11 | 0.0560.14 | 300.76 | 451.14 | 0.3330.85 | 5785 | 1.94.83 | 4.1816.22 | 59211501 |
| 1818 | 40.6640.66 | 0.09570.0957 | |||||||
| 1616 | 48.5148.51 | 0.08950.0895 |
Part numbers in this family (2)
Application & features
Southwire’s Instrumentation Cables Type TC-ER per UL 1277 are suitable for installations as outlined in NEC Article 336 for process control and instrumentation, control circuits for operation and interconnection of protective and signaling devices and for general use in manufacturing, industrial and commercial distribution systems. Cables are constructed with 7-strand tinned copper conductors insulated with Ethylene Propylene Rubber EPR. The paired conductors are colored black, white, and alpha-numeric printed. The overall assembly is covered with an aluminum polyester foil with 100% coverage and a tinned drain wire. The cable is suited for use in cable trays, raceways, conduit, aerial (when supported with a messenger) and direct burial. The cable is rated for -30°C to 90°C wet or dry and rated for Class I Div II hazardous locations, sun and oil resistant. The jacket is black Chlorinated Polyethylene CPE with a rip cord for easy removal. 1 Pair is not TC-ER Rated.
Standards & references
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1277 Electrical Power and Control Tray Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- EPA 40 CFR, Part 26, Subpart C heavy metals per Table 1, TCLP method