345 kV XLPE Laminate Power Cable

Southwire #
HVUD23

SW standard wall XLPE copper or aluminum laminate sheath, available up to 6,000 kcmil.

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Available sizes & constructions

Size (kcmil¹)(mm^2)Conductor Diameter (inches)(mm)Insulation Thickness (inch)(cm)Diameter Over Insulation (inch)(cm)Overall Jacket Diameter (inch)(cm)Min. Bend Radius (inch)(inch)CapacitanceCharging Current (A/kft)Cable Weight² (lbs/ft)Cable Weight² (lbs/ft)
125031.751.193.0212603200.403.889.864.6111.7183/5683/5638.3738.373.373.3710.8110.818.328.32
150038.101.323.3511812999.743.859.784.5711.6183/5583/5542.7542.753.723.7211.3711.378.348.34
175044.451.433.6311422900.683.889.864.6111.7183/5683/5645.7345.733.983.9812.1412.148.598.59
200050.801.503.8111422900.683.9510.034.6911.9185/5785/5747.3247.324.124.1213.0813.088.968.96
250063.501.734.3910632700.024.0510.294.7912.1787/5887/5854.5854.584.754.7514.6614.669.519.51
300076.201.894.8010632700.024.2810.875.0312.7891/6191/6159.1359.135.155.1516.6616.6610.4610.46
350088.902.075.2610632700.024.3811.135.1513.0893/6293/6261.2461.245.335.3318.4218.4211.1611.16
4000101.602.175.5110632700.024.4811.385.2513.3495/6395/6363.1963.195.505.5020.1420.1411.8311.83
5000127.002.486.3010632700.024.7912.175.5914.20101/68101/6869.3269.326.046.0424.5424.5413.3813.38
6000152.402.676.7810632700.024.9912.675.7914.71105/70105/7073.1373.136.376.3727.3027.3014.7814.78
125031.75920920637637770770533533730730506506620620430430
150038.1010101010700700840840582582810810561561680680471471
175044.4510901090755755900900624624880880610610730730506506
200050.8011501150797797950950658658940940651651780780540540
250063.50137013709499491110111076976911001100762762900900624624
300076.2015001500103910391220122084584512201220845845980980679679
350088.901600160011091109130013009019011320132091591510601060734734
4000101.601700170011781178137013709499491410141097797711301130783783
5000127.0018801880130313031500150010391039161016101115111512901290894894
6000152.4020002000138613861590159011021102177017701226122614001400970970

Application & features

Predominantly used for underground transmission in conduit systems, suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 345,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation.

Standards & references

  • Max Voltage Rating: 362 kV
  • BIL Rating: 1300 kV
  • Nominal Conductor: 90 °C
  • Max. Emergency Conductor: 105 °C
  • Short Circuit Conductor: 250 °C
  • Minimum Installation: -10 °C
  • Design Standards: AEIC, ICEA, IEC
  • Factory Test Voltages: 440 kV / 60 min.
  • XLPE Loss Factor: 0.0005
  • Relative Permittivity: 2.3