DistributorSouthwire

Southwire

350-37 TINNED CU TELCO L3 GREEN 2000 FT

Southwire #
57156901

Limited smoke, Non-halogenated Insulation, 105°C Dry, 60°C Wet

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

This specification covers the construction requirements for a limited smoke, non-halogenated power cable insulated with TelcoHyde® 5221 with an overall flame retardant saturated braid. UL listed Type RHH, FT4-ST1 in accordance with the National Electrical Code. Product is for use in Central Office, CATV Head End, Data Center and Cell Tower applications. Cable is suitable for UL “CT USE” (Cable Tray rated).

Specifications

Size350 KCMIL350 KCMIL
No. of Strands3737
Nominal Total Weight1305 lbs/1000'1942 kgs/km
Allowable Ampacity at 75C310310
Allowable Ampacity at 90C350350
Insulation Thickness95 mils2.41 mm
DC Resistance at 25°C0.032060.03206

Standards & references

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Type RHH, FT4-ST1, VW-1, 600 Volts DC or AC
  • UL 2731 Telecommunications Central Office Power Cable
  • CSA AWM IB 105°C 600V. FT4-ST1
  • IEC including 60674 and 60332
  • RoHS Complaint , Lead-Free, Silicone-Free
  • KS-24194™ List 3
  • ATIS-0600017.2014 Non-Halogenated DC Power Wire and Cable for Telecommunications Power Systems
  • Telcordia GR-347-CORE
  • REACH - European Community Regulation