DistributorSouthwire

Southwire

CL4SS 16/2 PAIR STR CU CL4Z/CMG PVC-LS BLACK 1000 FT

Southwire #
CL4Z162N0608

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Intended for use in Fault Managed Power Systems (FMPS), remote powering, indoor Class 4 circuits per 2023 National Electrical Code (NEC) article 726. For use, primarily, in Agriculture, Intelligent Buildings, and Wireless Densification. The power source (transmitter) for Class 4 circuits shall be supplied from a power source that has a voltage output of 450 volts (peak or DC) or less. The CL4Z cables are considered for outdoor use only and are not to be attached to or used within a building structure. Type CL4Z cables comply with the applicable requirements for CL4. The CMG cables can be installed in buildings according to NEC article 722.135 and table 722.135(B).

Ratings:
Normal operating temperature: 90°C
Temperature Range: -40°C to 90°C
Rated Use: Dry or wet locations

Specifications

Cond. Size16 AWG16 AWG
Conductor Number22
Cond. Strands1919
Diameter Over Conductor0.056 inch0.14 cm
Insulation Thickness17 mils0.43 mm
Jacket Thickness25 mils0.64 mm
Approx. OD0.376 inch0.96 cm
Approx. Weight70 lbs/1000'104 kgs/km
DC Resistance at 25C4.181 ohms/1000'6.22 ohms/km
Min. Bend Radius1.4 inch3.56 cm

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1400-2 Fault-Managed Power Systems - Part 2: Requirements for Cables
  • UL 444 Communications Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test