SERVICESOLAR® (PV) RHW-2 1,000/2,000 Volt Copper No Pulling Lubricant Required
PV2K750BK SERVICESOLAR® (PV) RHW-2 1,000/2,000 Volt Copper No Pulling Lubricant Required 750 kcmil
- Service Wire #
- PV2K750BK
Single copper conductor, stranded and insulated with moisture and heat resistant, chemically crosslinked polyethylene. Featuring ServicePRO-X ® Insulation–No Pulling Lubricant Required (#6 AWG and larger) . Rated 2kV to meet the challenging requirements of transformerless inverters on photovoltaic (solar) panel installations. Available in colors.
Part of the family: SERVICESOLAR® (PV) RHW-2 1,000/2,000 Volt Copper No Pulling Lubricant Required
Application & features
Application
Suitable for use as interconnection wiring on solar panels in grounded or ungrounded systems as defined in applicable parts of the National Electrical Code (NEC) NFPA 70, such as article 690.31(A). Suitable for use in 105°C dry systems. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade) .
Specifications
| Voltage Rating | 2 kV (2,000 V)2 kV |
|---|---|
| Certifications | CSA, REACH, ROHS, UL, USACSA, REACH, ROHS, UL, USA |
| Construction | 750 kcmil750 kcmil |
| Strand | 6161 |
| Insulation Thickness | 135135 |
| Nominal Diameter Overall | 1.261.26 |
| Approx. Net Weight | 2,5162,516 |
| Ampacity 90°C Wet/Dry | 885885 |
Standards & references
- ASTM Standards: B-3 (soft or annealed), B-8 (concentric lay stranded)
- B-787 (combination strand)
- UL 44 RHW-2, UL 854 USE-2, and UL 4703 PV Wire
- C(UL) RPVU90 1kV/2kV: CSA C22.2 #271
- ICEA S-95-658/NEMA WC-70
- Federal Spec. A-A-59544
- Flame Rated: Vertical Wire, CT Use (1/0 AWG and larger)
- Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
- Sunlight Resistant, Gasoline and Oil Resistant II
- Direct Burial
- RoHS Compliant
- NEMA BABA 70901-2-2024 WC-02-03, WC-02-04, WC-02-05