DistributorSouthwire

Service Wire

JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor

Service Wire #
SW-JACKETED-MC-2KV-3-CDRS

Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RHW-2) , phase identified and cabled together with suitable fillers (when required) and bare copper grounding conductor. Cable core covered with mylar binder tape and aluminum or galvanized steel interlocked armor with overall black PVC jacket. Jacket available under armor and in colors. Available with EnviroPlus ® (LSZH) jacket.

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (12) ↓

Available sizes & constructions

Size (AWG or Kcmil)(AWG or Kcmil)Strand (no.)(no.)Insulation Thickness (mils)(mm)Grounding Conductor (AWG)(AWG)Diameter Over Armor (in.)(mm)Jacket Thickness (mils)(mm)Approx. Diameter Overall (in.)(mm)Approx. Net Weight Aluminum Armor (lb./1000')(kg/km)Approx. Net Weight Galvanized Armor (lb./1000')(kg/km)Ampacity (30°C ambient)(30°C ambient)
6677852.16880.9925.1501.271.0927.76409527651,1387575 AAP2K6/3
4477852.16661.0927.7501.271.1930.28341,2419751,4519595 AAP2K4/3
2277852.16661.2732.3501.271.3734.81,1591,7251,4272,124130130 AAP2K2/3
11771052.67661.4135.8501.271.5138.41,4142,1041,7182,557145145 AAP2K1/3
1/01/019191052.67661.5138.4601.521.6341.41,7152,5522,0443,042170170 AAP2K1/03
2/02/019191052.67661.6140.9601.521.7343.92,1093,1392,4323,619195195 AAP2K2/03
3/03/019191052.67441.7143.4601.521.8346.52,4973,7162,8434,231225225 AAP2K3/03
4/04/019191052.67441.8547.0601.521.9750.02,9904,4503,3584,997260260 AAP2K4/03
25025037371203.05441.9750.0601.522.0953.13,5715,3143,9775,918290290 AAP2K250/3
35035037371203.05332.2156.1601.522.3359.24,7207,0245,1817,710350350 AAP2K350/3
50050037371203.05222.4762.7751.912.6266.56,6429,8846,97110,374430430 AAP2K500/3
75075061611353.43112.8973.4751.913.0477.29,28813,8229,90714,743535535 AAP2K750/3

Part numbers in this family (12)

By size:
Southwire #DescriptionConstructionStrandInsulation ThicknessGrounding ConductorDiameter Over ArmorJacket ThicknessApprox. Diameter OverallApprox. Net Weight Aluminum ArmorApprox. Net Weight Galvanized ArmorAmpacity
AAP2K6/3AAP2K6/3 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 6 AWG 3C6 AWG 3C78580.99501.0964076575
AAP2K4/3AAP2K4/3 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 4 AWG 3C4 AWG 3C78561.09501.1983497595
AAP2K2/3AAP2K2/3 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 2 AWG 3C2 AWG 3C78561.27501.371,1591,427130
AAP2K1/3AAP2K1/3 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 1 AWG 3C1 AWG 3C710561.41501.511,4141,718145
AAP2K1/03AAP2K1/03 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 1/0 AWG 3C1/0 AWG 3C1910561.51601.631,7152,044170
AAP2K2/03AAP2K2/03 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 2/0 AWG 3C2/0 AWG 3C1910561.61601.732,1092,432195
AAP2K3/03AAP2K3/03 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 3/0 AWG 3C3/0 AWG 3C1910541.71601.832,4972,843225
AAP2K4/03AAP2K4/03 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 4/0 AWG 3C4/0 AWG 3C1910541.85601.972,9903,358260
AAP2K250/3AAP2K250/3 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 250 kcmil 3C250 kcmil 3C3712041.97602.093,5713,977290
AAP2K350/3AAP2K350/3 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 350 kcmil 3C350 kcmil 3C3712032.21602.334,7205,181350
AAP2K500/3AAP2K500/3 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 500 kcmil 3C500 kcmil 3C3712022.47752.626,6426,971430
AAP2K750/3AAP2K750/3 JACKETED MC RHW-2/PVC 2,000 Volt Copper 3 Conductor 750 kcmil 3C750 kcmil 3C6113512.89753.049,2889,907535

Application & features

Application

Suitable for use in industrial power distribution systems where continuity of service is the prime consideration. May be installed in wet or dry locations, directly buried, or encased in concrete. Suitable for use in cable tray. Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2.

Specifications

Voltage Rating2 kV (2,000 V)2 kV
CertificationsREACH, ROHS, UL, USAREACH, ROHS, UL, USA

Standards & references

  • UL 44, UL 854, and UL 1569
  • ICEA S-95-658/NEMA WC-70
  • Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU),
  • IEEE 1202/CSA FT-4, Two-hour Firewall
  • Temperature Rated at 90°C Wet /Dry
  • Sunlight Resistant, Gasoline and Oil Resistant II Jacket
  • Direct Burial (includes encasement in concrete)
  • Color Code: Black and Numbered (optional color codes available)
  • RoHS Compliant
  • NEMA BABA 70901-2-2024 WC-02-03, WC-02-04, WC-02-05