DistributorSouthwire

Southwire

Flexible CU 2000V XLPE Insulation Three Grounds Cu Tape Shield PVC Jacket. RHH/RHW-2 Variable Frequency Drive (VFD)

Southwire #
SPEC45453

Type TC-ER VFD Power Cable 2000Volt Three Conductor Flexible Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 Polyvinyl Chloride (PVC) Jacket with 3 Symmetrical Bare CU Ground 50% Minimum Tape Shield Overlap. Rated 90C Dry or We. Sunlight Resistance, Direct Burial, Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (6) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Shield (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)
262.6 KCMIL262.6 KCMIL336466460.5651.441052.671.7484.441102.791.9685.003106462241256139 67462599
313.3 KCMIL313.3 KCMIL337797790.6501.651102.791.9044.841403.562.1845.553635540948887274 65304799
373.7 KCMIL373.7 KCMIL339319310.7011.781052.672.0075.101102.792.2275.664162619453888018 67463299
500 KCMIL500 KCMIL33122512250.8582.181102.792.3485.961152.922.5786.5556388390685110195 66854199
535.3 KCMIL535.3 KCMIL33134913490.8592.181203.052.3966.091102.792.6166.6458768744744811084 67463899
777.7 KCMIL777.7 KCMIL33192419240.9662.451253.182.7637.021403.563.0437.739082135161086516169 67310999
262.6 KCMIL262.6 KCMIL3323.659.9463022858.540.0480.070.0580.090.0220.030.0410.06267267304304 67462599
313.3 KCMIL313.3 KCMIL3326.266.5575193410.560.0390.060.0480.070.0200.030.0410.06298298332332 65304799
373.7 KCMIL373.7 KCMIL3326.767.8289684067.810.0330.050.0420.060.0180.030.0400.06323323365365 67463299
500 KCMIL500 KCMIL3330.978.4910000045359.200.0230.030.0310.050.0150.020.0390.06380380430430 66854199
535.3 KCMIL535.3 KCMIL3331.479.7610000045359.200.0210.030.0280.040.0170.030.0390.06394394446446 67463899
777.7 KCMIL777.7 KCMIL3336.592.7110000045359.200.0160.020.0240.040.0150.020.0380.06483483543543 67310999

Part numbers in this family (6)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
67462599262.6-646 3/C CU RHH-RHW-2 3X#2 GW T/S PVC JKT TC-ER 2000V VFD262.6 KCMIL 3C 646S1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
65304799313.3-779 3/C CU RHH-RHW-2 3X#2 GW T/S PVC JKT TC-ER 2000V VFD313.3 KCMIL 3C 779S1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
67463299373.7-931 3/C CU RHH-RHW-2 3X#2 GW T/S PVC JKT TC-ER 2000V VFD373.7 KCMIL 3C 931S1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
66854199500-1221 3/C CU RHH-RHW-2 3X#1 GW T/S PVC JKT TC-ER 2000V VFD500 KCMIL 3C 1221S1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
67463899535.3-1332 3/C CU RHH-RHW-2 3X#2 GW T/S PVC JKT TC-ER 2000V VFD535.3 KCMIL 3C 1332S1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL
67310999777.7-1924 3/C CU RHH-RHW-2 3X#2/0 GW T/S PVC JKT TC-ER 2000V VFD - COLLINS AEROSPACE777.7 KCMIL 3C 1924S1-BLACK/2-RED/3-BLUECUT TO LENGTH REEL

Application & features

Southwire’s 2000 Volt Type TC-ER VFD power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® Article 336.10.

Standards & references

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 TC-ER
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA S-138-738 Power Cables Rated 2000 Volts or Less for use Between Variable Frequency Drives and Motors
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661