DistributorSouthwire

Southwire

CU Compressed 5/8kV NLEPR Insulation 133/100% IL SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial

Southwire #
SPEC46102

Type MV-105 Single Conductor Copper, 5kV 133% /8KV 100% 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA.

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (16) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Diameter Over Insulation (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Shield (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)Conduit Size (in)(cm)
2 AWG2 AWG770.2820.720.5451.381152.920.6051.54551.400.7551.92454676530240.409.022.862.56.35 95463699
1 AWG1 AWG19190.3220.820.5901.501152.920.6501.65551.400.8002.03527784669303.459.624.382.56.35 95464499
1/0 AWG1/0 AWG19190.3610.920.6301.601152.920.6901.75802.030.8702.21639951844382.8310.426.422.56.35 95500599
2/0 AWG2/0 AWG19190.4051.030.6741.711152.920.7341.86802.030.9142.3274511091064482.6210.927.693.07.62 95501399
3/0 AWG3/0 AWG19190.4561.160.7241.841152.920.7841.99802.030.9642.4587713051342608.7211.529.213.07.62 95502199
4/0 AWG4/0 AWG19190.5121.300.7801.981152.920.8402.13802.031.0202.59103915461692767.4812.230.993.07.62 95508899
250 KCMIL250 KCMIL37370.5581.420.8182.081152.920.8782.23802.031.0582.69117917552000907.1812.632.003.07.62 95503999
350 KCMIL350 KCMIL37370.6611.680.9372.381152.920.9972.53802.031.1772.991548230428001270.0614.135.813.58.89 95504799
500 KCMIL500 KCMIL37370.7892.001.0422.651152.921.1022.80802.031.2823.262063307040001814.3715.338.864.010.16 95505401
600 KCMIL600 KCMIL61610.8652.201.1522.931152.921.2123.08802.031.3923.542431361848002177.2416.742.424.010.16 67963899
750 KCMIL750 KCMIL61610.9682.461.2543.191152.921.3143.34802.031.4943.792946438460002721.5517.945.474.511.43 95509601
1000 KCMIL1000 KCMIL61611.1172.841.4033.561152.921.4633.72802.031.6434.173793564580003628.7419.750.045.012.70 95507099
2 AWG2 AWG0.1620.240.2040.300.0340.050.0440.070.346 + j0.2340.346 + j0.2340.024 + j0.0370.024 + j0.03719201920145145155155190190215215 95463699
1 AWG1 AWG0.1280.190.1620.240.0310.050.0420.060.347 + j0.2190.347 + j0.2190.034 + j0.0400.034 + j0.04020442044170170180180225225250250 95464499
1/0 AWG1/0 AWG0.1020.150.1280.190.0280.040.0420.060.348 + j0.2140.348 + j0.2140.040 + j0.0430.040 + j0.04321652165195195210210260260290290 95500599
2/0 AWG2/0 AWG0.0810.120.1020.150.0260.040.0400.060.348 + j0.2300.348 + j0.2300.027 + j0.0350.027 + j0.03523022302220220235235300300330330 95501399
3/0 AWG3/0 AWG0.0640.100.0810.120.0240.040.0390.060.348 + j0.2300.348 + j0.2300.027 + j0.0360.027 + j0.03624592459250250270270345345385385 95502199
4/0 AWG4/0 AWG0.0510.080.0650.100.0210.030.0380.060.351 + j0.2270.351 + j0.2270.034 + j0.0390.034 + j0.03926332633290290310310400400445445 95508899
250 KCMIL250 KCMIL0.0430.060.0560.080.0200.030.0370.060.348 + j0.2340.348 + j0.2340.027 + j0.0400.027 + j0.04028002800320320345345445445495495 95503999
350 KCMIL350 KCMIL0.0310.050.0410.060.0180.030.0350.050.349 + j0.2450.349 + j0.2450.020 + j0.0340.020 + j0.03431203120385385415415550550615615 95504799
500 KCMIL500 KCMIL0.0220.030.0300.040.0150.020.0330.050.350 + j0.2460.350 + j0.2460.020 + j0.0330.020 + j0.03335163516470470505505695695775775 95505401
600 KCMIL600 KCMIL0.0180.030.0260.040.0140.020.0330.050.464 + j0.4900.464 + j0.4900.102 + j0.0410.102 + j0.04137823782505505544544777777865865 67963899
750 KCMIL750 KCMIL0.0140.020.0230.030.0130.020.0320.050.351 + j0.2270.351 + j0.2270.034 + j0.0400.034 + j0.0404102410258558563063090090010001000 95509601
1000 KCMIL1000 KCMIL0.0110.020.0190.030.0110.020.0310.050.350 + j0.2460.350 + j0.2460.020 + j0.0330.020 + j0.033456345636706707207201075107512001200 95507099

Part numbers in this family (16)

By size:
Southwire #DescriptionConstructionPackaging
2 AWG (1)
954636992-7 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA2 AWG 1C 7SCUT TO LENGTH REEL
1 AWG (1)
954644991-19 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA1 AWG 1C 19SCUT TO LENGTH REEL
1/0 AWG (1)
955005991/0-19 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA1/0 AWG 1C 19SCUT TO LENGTH REEL
2/0 AWG (1)
955013992/0-19 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA2/0 AWG 1C 19SCUT TO LENGTH REEL
3/0 AWG (1)
955021993/0-19 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL3/0 AWG 1C 19SCUT TO LENGTH REEL
4/0 AWG (1)
955088994/0-19 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA4/0 AWG 1C 19SCUT TO LENGTH REEL
250 kcmil (1)
95503999250-37 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA250 KCMIL 1C 37SCUT TO LENGTH REEL
350 kcmil (1)
95504799350-37 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA350 KCMIL 1C 37SCUT TO LENGTH REEL
500 kcmil (3)
95505499500-37 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA500 KCMIL 1C 37SCUT TO LENGTH REEL
95505477500-37 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA 0 FT500 KCMIL 1C 37SCUT TO LENGTH REEL
95505401500-37 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA 1000 FT500 KCMIL 1C 37S1000 FT REEL
600 kcmil (1)
67963899600-61 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA600 KCMIL 1C 61SCUT TO LENGTH REEL
750 kcmil (3)
95509699750-61 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA750 KCMIL 1C 61SCUT TO LENGTH REEL
95509677750-61 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA 0 FT750 KCMIL 1C 61SCUT TO LENGTH REEL
95509601750-61 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA 1000 FT750 KCMIL 1C 61S1000 FT REEL
1000 kcmil (1)
955070991000-61 CU 115 MILS NL-EPR 5KV 133%/8KV 100% T/S BLACK SIMpull PVC JACKET UL/CSA1000 KCMIL 1C 61SCUT TO LENGTH REEL

Application & features

Southwire’s 5kV 133% /8KV 100% cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), aerially supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold bend and cold impact. Marked with "LTDD" CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemicals, oils and acids and are flame retardant.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661