DistributorSouthwire

Southwire

CU Compressed 25kV NLEPR Insulation 133% IL Black PVC Jacket. MV 105 - UL Tray Rated - Sunlight Resistant - For Direct Burial

Southwire #
SPEC46602

Type MV-105 Three Conductor Copper, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA. Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (4) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Diameter Over Insulation (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Shield (in)(cm)Ground SizeJacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)
1/0 AWG1/0 AWG19190.3610.921.0402.643208.131.1002.791x61x61102.792.6496.733505521625341149.4018.546.99 64737999
250 KCMIL250 KCMIL37370.5581.421.2443.163208.131.3043.311x21x21353.433.1107.905667843360002721.5521.755.12 67260399
350 KCMIL350 KCMIL37370.6611.681.3473.423208.131.4073.571x21x21353.433.3648.5468181014684003810.1723.559.69 67320499
500 KCMIL500 KCMIL37370.7892.001.4523.693208.131.5123.841x11x11353.433.5949.13880213099120005443.1025.163.75 67930599
1/0 AWG1/0 AWG0.1020.150.1280.190.0550.080.0480.070.450 + j0.3920.450 + j0.3920.081 + j0.0410.081 + j0.04134353435195195210210215215240240 64737999
250 KCMIL250 KCMIL0.0430.060.0560.080.0410.060.0420.060.450 + j0.3920.450 + j0.3920.081 + j0.0410.081 + j0.04140714071310310335335360360400400 67260399
350 KCMIL350 KCMIL0.0310.050.0410.060.0370.060.0390.060.450 + j0.3920.450 + j0.3920.081 + j0.0410.081 + j0.04143904390375375400400435435490490 67320499
500 KCMIL500 KCMIL0.0220.030.0300.040.0320.050.0370.060.450 + j0.3920.450 + j0.3920.081 + j0.0410.081 + j0.04147864786450450485485535535600600 67930599

Part numbers in this family (4)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
647379991/0-19 3/C CU 320 MILS NL-EPR 25KV 133% T/S 1X4 CU GW BLACK PVC UL/CSA1/0 AWG 3C 19 STRBLACK-/BLACK-/BLACK-/-CUT TO LENGTH REEL
67260399250-37 3/C CU 320 MILS NL-EPR 25KV 133% T/S 1X2 CU GW BLACK PVC UL/CSA 0 FT250 KCMIL 3C 37SBLACK-/BLACK-/BLACK-/-CUT TO LENGTH REEL
67320499350-37 3/C CU 320 MILS NL-EPR 25KV 133% T/S 1X2 CU GW BLACK PVC UL350 KCMIL 3C 37 STRBLACK-/BLACK-/BLACK-/-CUT TO LENGTH REEL
67930599500-37 3/C CU 320 MILS NL-EPR 25KV 133% T/S 1X1 CU GW BLACK PVC UL/CSA500 KCMIL 3C 37SBLACK-/BLACK-/BLACK-/-CUT TO LENGTH REEL

Application & features

Southwire’s 25KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed or dual UL/CSA listed. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661