DistributorSouthwire

Southwire

4/0-19 3/C CPRESS CU NL-EPR 3X#6 CU GW ARMOR-X MC 2.4KV 100% YELLOW PVCJACKET 2500 FT

Southwire #
89061889

Type MV-105 Three Conductor Copper, 90 Mils Ethylene Propylene Rubber (EPR) Continuous Corrugated Welded Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket. Suitable for VFD Applications. Type MC-HL. Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire’s 2.4KV ARMOR-X® Type MC-HL are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial or concrete encasement and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.

Specifications

Cond. Size4/0 AWG4/0 AWG
Cond. Strands1919
Diameter Over Conductor0.512 inch1.30 cm
Diameter Over Insulation0.715 inch1.82 cm
Insulation Thickness90 mils2.29 mm
Ground Size3 x 63 x 6
Diameter Over Armor1.870 inch4.75 cm
Jacket Thickness60 mils1.52 mm
Approx. OD1.990 inch5.05 cm
Approx. Weight3199 lbs/1000'4761 kgs/km
Max Pull Tension5078 lbs2303.34 kg
Min. Bend Radius13.9 inch35.31 cm

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661