1/0-19 3/C CPRESS CU NL-EPR 3X#8 CU GW ARMOR-X MC 2.4KV 100% YELLOW PVCJACKET
- Southwire #
- 89061699
Type MV-105 Three Conductor Copper, 90 Mils Ethylene Propylene Rubber (EPR) Continuous Corrugated Welded Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket. Suitable for VFD Applications. Type MC-HL. Silicone Free
Part of the family: CU Compressed 2.4kV NLEPR Insulation 100% IL ARMOR-X® PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial - VFD Cable
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 2.4KV ARMOR-X® Type MC-HL are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial or concrete encasement and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.
Specifications
| Cond. Size | 1/0 AWG1/0 AWG |
|---|---|
| Cond. Strands | 1919 |
| Diameter Over Conductor | 0.361 inch0.92 cm |
| Diameter Over Insulation | 0.580 inch1.47 cm |
| Insulation Thickness | 90 mils2.29 mm |
| Ground Size | 3 x 83 x 8 |
| Diameter Over Armor | 1.540 inch3.91 cm |
| Jacket Thickness | 60 mils1.52 mm |
| Approx. OD | 1.660 inch4.22 cm |
| Approx. Weight | 1960 lbs/1000'2917 kgs/km |
| Max Pull Tension | 2534 lbs1149.40 kg |
| Min. Bend Radius | 11.6 inch29.46 cm |
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- UL 1072 Medium-Voltage Power Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
- ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661