
![]()
1/0-19 3/C CU 220 MILS TR-XLP 15KV 133% T/S 1X4 CU GW BLACK PVC UL
- Southwire #
- 67348899
Type MV-105 Three Conductor Copper, 220 Mils Tree Retardant Cross Linked Polyethylene (TRXLPE) 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Jacket. Silicone Free
Part of the family: CU Compressed 15kV TRXLPE Insulation 133% IL Black PVC Jacket. MV 105 - Sunlight Resistant - For Direct Burial
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications
| Cond. Size | 1/0 AWG1/0 AWG |
|---|---|
| Cond. Strands | 1919 |
| Diameter Over Conductor | 0.361 inch0.92 cm |
| Diameter Over Insulation | 0.840 inch2.13 cm |
| Insulation Thickness | 220 mils5.59 mm |
| Diameter Over Shield | 0.900 inch2.29 cm |
| Ground Size | 1x41x4 |
| Jacket Thickness | 110 mils2.79 mm |
| Approx. OD | 2.222 inch5.64 cm |
| Approx. Weight | 2767 lbs/1000'4118 kgs/km |
| Max Pull Tension | 2534 lbs1149.40 kg |
| Min. Bend Radius | 15.5 inch39.37 cm |
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- UL 1072 Medium-Voltage Power Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661