350-37 3/C CPRESS CU NL-EPR 25% T/S 3X#6 CU GW ARMOR-X MC-HL OR MV-105 15KV 133% RED PVC JACKET 0 FT

Southwire #
45834799

Type MV-105 Three Conductor Copper, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Three Grounds, Continuous Corrugated Welded Aluminum Armor. -ARMOR-X®, Polyvinyl Chloride (PVC) Jacket. Suitable For VFD Applications. Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire’s 15KV ARMOR-X® with 50% ground are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Cable is suitable for VFD applications

Specifications

Cond. Size350 KCMIL350 KCMIL
Cond. Strands3737
Diameter Over Conductor0.661 inch1.68 cm
Diameter Over Insulation1.127 inch2.86 cm
Insulation Thickness220 mils5.59 mm
Diameter Over Shield1.187 inch3.01 cm
Ground Size3x63x6
Diameter Over Armor3.220 inch8.18 cm
Jacket Thickness85 mils2.16 mm
Approx. OD3.390 inch8.61 cm
Approx. Weight7406 lbs/1000'11021 kgs/km
Max Pull Tension8400 lbs3810.17 kg
Min. Bend Radius23.7 inch60.20 cm

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • ABS Listed as CWCMC